Performance data (cont)
HEATING CAPACITIES (cont)
50HS036 (3 TONS)
Temp (F)
Air Ent
Indoor
Coil
Indoor
Air
Cfm
(std)
Air Temp Entering Outdoor Coil (F db at 70% rh)
1001017203040475060
60
1050
Cap. 3.94 3.94 9.13 9.13 14.30 13.50 17.90 16.40 19.50 17.60 24.70 21.60 31.30 30.00 35.80 35.80 37.90 37.90 44.90 44.90
kW 2.29 2.44 2.60 2.70 2.75 2.90 3.08 3.20 3.25 3.41
1300
Cap. 4.19 4.19 9.52 9.52 14.90 14.00 18.60 17.00 20.20 18.20 25.50 22.40 32.30 31.00 37.10 37.10 39.20 39.20 46.20 46.20
kW 2.41 2.55 2.68 2.78 2.82 2.96 3.12 3.22 3.26 3.40
1500
Cap. 4.33 4.33 9.76 9.76 15.20 14.40 19.00 17.30 20.60 18.60 26.10 22.90 33.00 31.60 37.80 37.80 39.90 39.90 46.80 46.80
kW 2.49 2.62 2.75 2.84 2.88 3.01 3.16 3.26 3.29 3.41
70
1050
Cap. 3.21 3.21 8.23 8.23 13.20 12.50 16.80 15.30 18.30 16.50 23.30 20.40 29.70 28.50 34.20 34.20 36.40 36.40 43.60 43.60
kW 2.29 2.47 2.64 2.76 2.81 2.98 3.18 3.32 3.38 3.58
1300
Cap. 3.43 3.43 8.60 8.60 13.80 13.00 17.40 15.90 19.00 17.10 24.10 21.10 30.80 29.50 35.40 35.40 37.60 37.60 44.80 44.80
kW 2.41 2.57 2.72 2.83 2.88 3.04 3.22 3.34 3.39 3.56
1500
Cap. 3.62 3.62 8.88 8.88 14.10 13.40 17.80 16.30 19.40 17.50 24.70 21.60 31.40 30.20 36.10 36.10 38.30 38.30 45.40 45.40
kW 2.50 2.65 2.80 2.90 2.95 3.10 3.26 3.38 3.42 3.56
80
1050
Cap. 1.77 1.77 6.81 6.81 11.90 11.20 15.40 14.00 16.90 15.20 21.90 19.20 28.10 27.00 32.50 32.50 34.60 34.60 41.70 41.70
kW 2.28 2.47 2.67 2.80 2.86 3.05 3.27 3.42 3.49 3.71
1300
Cap. 2.18 2.18 7.32 7.32 12.50 11.80 16.00 14.60 17.60 15.80 22.70 19.90 29.10 28.00 33.60 33.60 35.80 35.80 43.20 43.20
kW 2.40 2.58 2.76 2.88 2.93 3.11 3.31 3.45 3.51 3.71
1500
Cap. 2.49 2.49 7.67 7.67 12.90 12.20 16.50 15.00 18.00 16.30 23.20 20.40 29.80 28.60 34.40 34.40 36.60 36.60 43.80 43.80
kW 2.49 2.66 2.83 2.95 3.00 3.17 3.36 3.49 3.54 3.72
50HS042 (3
1
2
TONS)
Temp (F)
Air Ent
Indoor
Coil
Indoor
Air
Cfm
(std)
Air Temp Entering Outdoor Coil (F db at 70% rh)
100 1017203040475060
60
1225
Cap. 14.80 13.60 18.30 16.80 22.20 20.40 25.20 23.00 26.70 24.20 31.70 27.80 37.10 37.10 41.80 41.80 42.80 42.80 47.30 47.30
kW 2.28 2.47 2.68 2.82 2.89 3.12 3.37 3.60 3.64 3.85
1440
Cap. 15.20 13.90 18.70 17.20 22.70 20.80 25.70 23.40 27.20 24.70 32.30 28.30 37.70 37.70 41.80 41.80 42.80 42.80 46.30 46.30
kW 2.34 2.53 2.73 2.87 2.93 3.16 3.40 3.57 3.62 3.77
1575
Cap. 15.50 14.20 19.00 17.50 23.00 21.20 26.10 23.80 27.60 25.00 32.70 28.70 38.20 38.20 41.40 41.40 42.00 42.00 45.50 45.50
kW 2.40 2.59 2.78 2.92 2.98 3.20 3.44 3.56 3.59 3.73
70
1225
Cap. 13.60 12.50 17.30 15.90 21.20 19.40 24.00 21.90 25.50 23.10 30.30 26.60 35.60 35.60 40.20 40.20 41.50 41.50 46.70 46.70
kW 2.29 2.51 2.75 2.91 2.98 3.23 3.50 3.73 3.81 4.06
1400
Cap. 13.90 12.80 17.60 16.20 21.60 19.80 24.50 22.30 26.00 23.50 30.90 27.10 36.30 36.30 40.80 40.80 42.00 42.00 46.50 46.50
kW 2.36 2.57 2.80 2.95 3.03 3.27 3.53 3.76 3.81 4.02
1575
Cap. 14.30 13.10 18.00 16.50 22.00 20.20 24.90 22.70 26.40 23.90 31.40 27.50 36.80 36.80 41.10 41.10 41.90 41.90 45.80 45.80
kW 2.42 2.63 2.85 3.00 3.07 3.31 3.56 3.76 3.80 3.97
80
1225
Cap. 12.20 11.20 16.00 14.70 19.90 18.30 22.80 20.80 24.20 22.00 28.90 25.30 34.00 34.00 38.60 38.60 39.80 39.80 45.80 45.80
kW 2.30 2.54 2.79 2.98 3.06 3.33 3.62 3.86 3.95 4.27
1400
Cap. 12.50 11.50 16.40 15.10 20.50 18.80 23.30 21.30 24.70 22.40 29.50 25.80 34.70 34.70 39.20 39.20 40.60 40.60 45.90 45.90
kW 2.36 2.60 2.85 3.02 3.10 3.37 3.65 3.88 3.97 4.23
1575
Cap. 12.80 11.80 16.70 15.40 20.90 19.10 23.70 21.60 25.10 22.80 30.00 26.30 35.30 35.30 39.80 39.80 40.90 40.90 45.50 45.50
kW 2.42 2.66 2.91 3.07 3.15 3.41 3.68 3.92 3.98 4.19
LEGEND
Cap. Heating Capacity (1000 Btuh) (Includes Indoor-Fan Motor Heat)
db Dry Bulb
kW Total Power Input (Includes Compressor Motor Power Input, Outdoor-
Fan Motor Input, and Indoor-Fan Motor Input)
rh Relative Humidity
NOTES:
1. indicates integrated ratings.
2. Integrated capacity is maximum (instantaneous) capacity less the effect of frost
on the outdoor coil and the heat required to defrost it.