UNIT
ELECTRICAL
CHARACTERISTICS
UNIT WT CORNER WT (Lb/Kg)
Lb Kg A B C D
50HS048 208/230-1-60, 208/230-3-60, 460-3-60 379 172 94/43 86/39 118/54 81/37
50HS060 208/230-1-60, 208/230-3-60, 460-3-60 393 179 97/44 90/41 121/55 85/39
UNIT
CENTER OF GRAVITY (in./mm)
XYZ
50HS048 19.6/498 20.6/524 17.3/440
50HS060 19.6/497 20.6/524 17.3/440
REQ’D CLEARANCES FOR SERVICING — in. (mm)
Indoor Coil Access Side .................30(762)
Control Box Access Side ................30(762)
(Except for NEC requirements)
Unit Top .........................36(914)
Side Opposite Ducts ..................30(762)
REQ’D CLEARANCES TO COMBUSTIBLE MAT’L — in. (mm)
Unit Top .............................0
Duct Side of Unit ........................0
Side Opposite Ducts ......................0
Bottom of Unit .........................0
Vertical Discharge, First 12 in. (305) of Supply Duct . . . 1 (25)
NEC REQ’D CLEARANCES — in. (mm)
Between Units, Control Box Side ...........42(1067)
Unit and Ungrounded Surfaces, Control Box Side . . . .36 (914)
Unit and Block or Concrete Walls and Other
Grounded Surfaces, Control Box Side ........42(1067)
LEGEND
CG — Center of Gravity
MAT’L — Material
NEC — National Electrical Code
REQ’D — Required
Fig. 5 — Dimensions; Sizes 048,060; With Optional Base Rail
NOTE: Clearances must be maintained to prevent
recirculation of air from outdoor-fan discharge.
5