2. Coil Options:
Shall include factory --installed optional copper/copper and
vinyl--coated refrigerant coils.
3. Economizer:
a. Economizer controls capable of providing free cooling
using outside air.
b. Equipped with low leakage dampers not to exceed 3%
leakage, at 1.0 in. wc pressure differential.
c. Spring return motor shuts off outdoor damper on power
failure.
4. Flat Roof Curb:
Curbsshall have seal strip and a wood nailerfor flashing and
shall be installed per manufacturer’s instructions.
5. Manual Outdoor Air Damper:
Package shall consist of damper, birdscreen, and rainhood
which can be preset to admit outdoor air foryear--round ven-
tilation.
6. 6. Thermostat:
To provide for one--stage heating and cooling in addition
manual or automatic changeover and indoor fan control.
7. Low Ambient Package:
Shall consist of a solid--state control and outdoor coil tem-
perature sensor for controlling outdoor--fan motor opera-
tion, which shall allow unit to operate down to 0_F
(--17.7_C) outdoor ambient temperature.
8. Filter Rack Kit:
Shall provide filter mounting for downflow applications.
9. Controls Upgrade Kit:
Shall provide high and low pressure safety protection.
10. Square--To--Round Duct Transitions (024--048):
Shall have the ability to convert the supply and return open-
ings from rectangular to round.
11. Crankcase Heater:
Shallprovideanti--floodback protectionfor lowload cooling
applications.
12. Electric heaters:
a. Electric heater shall be available as a fieldinstalled option.
b. Heater elements shall be open wire type, adequately
supported and insulated with ceramic bushings.
c. Electric heater packages must provide single point power
connection capability.
50SZ

Other manuals for Carrier 50SZ Series