EasyManua.ls Logo

Carrier 50TCQA - Page 19

Carrier 50TCQA
48 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
19
Outdoor Air Temperature (OAT) Sensor The OAT is
fact ory--mounted in the EconoMi$er2 (FIOP or
accessory). It is a nominal 10k ohm thermistor attached to
an eyelet mounting ring.
EconoMi$er2 The PremierLink control is used with
EconoMi$er2 (option or accessory) for outdoor air
management. The damper position is controlled directly
by the PremierLink control; EconoMi$er2 has no internal
logic device.
Outdoor air manage ment functi ons can be enhanced with
field--installation of these accessory control devices:
Enthalpy control ( outdoor air or differential sensors)
Space CO
2
sensor
Outdoor air CO
2
sensor
Refer to Table 3 for accessory part numbers.
Field connections Field connections for accessory
sensor and input de vices are made at the 16--pole terminal
block (TB1) located on the control box bot tom shelf in
front of the PremierLink control (See Fig. 30). Some input
devices also require a 24--vac signal source; connect at
CTB terminal R at “THERMOSTAT” connection strip for
this signal source. See connections figures on following
pages for field connection locations (and for continued
connec tions at the Premie rLink board i nputs).
Table 4 provide s a summary of field connections for units
equipped with Space Sensor. Table 5 provides a summary
of field connections for units e quipped with Space
Thermostat.
Space Sensors -- The PremierLink controller is
factory--shipped configured for Space Sensor Mode. A
Carrie r T--55 or T--56 space sensor must be used. T--55
space temperature sensor provides a signal of space
temperature to the PremierLink control. T--56 provides
same space temperature signal plus it a llows for
adjustment of space temperature setpoints from the face of
the sensor by the oc cupants.
2
3
45
61
SW1
SEN
BRN (GND)
BLU (SPT)
RED(+)
WHT(GND)
BLK(-)
CCN COM
SENSOR WIRING
C08201
Fig. 31 -- T--55 Space Temperature Sensor Wiring
Connect T--55 -- See Fig. 31 for typical T--55 internal
connec tions. Connect the T--55 SEN terminals to TB1
terminals 1 and 3 (see Fig. 32).
SEN J6-7
J6-6
1
3
TB1 PL
SEN
C08212
Fig. 32 -- PremierLink T--55 Sensor
Connect T--56 -- See Fig. 33 for T--56 internal
connec tions. Install a jumper between SEN and SET
terminals as illustrated. Connect T--56 terminals to TB1
terminals 1, 3 and 5 (see Fig. 34).
2
3
45
61
SW1
SEN
SET
Cool Warm
BRN (GND)
BLU (SPT)
RED(+)
WHT(GND)
BLK(-)
CCN COM
SENSOR WIRING
JUMPER
TERMINALS
AS SHOWN
BLK
(T56)
C08202
Fig. 33 -- T--56 Internal Connections
SEN J6-7
J6-6
1
3
TB1 PL
SEN
SET
Jumper
TB1
PL
J6-5
5
SET
C08213
Fig. 34 -- PremierLink T--56 Sensor
Connect Thermostat A 7--wire thermostat connec tion
requires a 24--v power source and a common connection.
Use the R and C terminals on the CTB’s THERMOSTAT
connec tion strip for the se. Connect the thermostats Y1,
Y2, W 1, W2 and G terminals to PremierLink TB1 as
shown in Fig. 35.
If the 50TCQ unit is equipped with factory--installed
smoke detector(s), disconnect the factory BLU lead at
TB1--6 (Y2) before connecting the thermostat. Ide ntify the
BLU lead originating at CTB--DDC--1; disconnect at
TB1--6 and tape off. Confirm that the second BLU lead at
TB1--6 remains connected to PremierLink J4--8.
50TCQA

Related product manuals