FAN PERFORMANCE (SI) — VERTICAL DISCHARGE UNITS
LEGEND
NOTES:
1. Boldface indicates field-supplied drive required (see Note 3).
2. indicates field-supplied motor and drive required.
3. Factory-shipped drive range is 15.50 to 20.08 r/s. Other r/s’s may
require a field-supplied drive.
4. Values include losses for filters, unit casing, and wet coils.
5. Extensive motor and electrical testing on these units ensures that
the full range of the motor can be utilized with confidence. Using
your fan motors up to the kW ratings shown will not result in
nuisance tripping or premature motor failure. Unit warranty will not
be affected. See Evaporator-Fan Motor Performance table on
page 30 or additional information.
6. Use of a field-supplied motor may affect wire sizing. Contact your
Carrier representative to verify.
7. To convert kW to bkW:
BkW = kW x Motor Efficiency
Motor Efficiency: .81 Maximum Continuous kW: 2.12
8. Interpolation is permissible. Do not extrapolate.
9. Static pressure losses (i.e., economizer, electric heater) must be
added to external static pressure before entering Fan Performance
table.
LEGEND
NOTES:
1. Boldface indicates field-supplied drive required (see Note 3).
2. indicates field-supplied motor and drive required.
3. Factory-shipped drive range is 10.33 to 14.67 r/s. Other r/s’s may
require a field-supplied drive.
4. Values include losses for filters, unit casing, and wet coils.
5. Extensive motor and electrical testing on these units ensures that
the full range of the motor can be utilized with confidence. Using
your fan motors up to the kW ratings shown will not result in
nuisance tripping or premature motor failure. Unit warranty will not
be affected. See Evaporator-Fan Motor Performance table on
page 30 or additional information.
6. Use of a field-supplied motor may affect wire sizing. Contact your
Carrier representative to verify.
7. To convert kW to bkW:
BkW = kW x Motor Efficiency
Motor Efficiency: .81 Maximum Continuous kW: 2.12
8. Interpolation is permissible. Do not extrapolate.
9. Static pressure losses (i.e., economizer, electric heater) must be
added to external static pressure before entering Fan Performance
table.
50TFF007 (17.6 kW)—STANDARD MOTOR (BELT DRIVE)
Airflow
(L/s)
External Static Pressure (Pa)
25 50 100 150 200 250 300 350 400
R/s kW R/s kW R/s kW R/s kW R/s kW R/s kW R/s kW R/s kW R/s kW
700 12.1 0.3013.1 0.36 14.8 0.48 16.4 0.61 17.8 0.75 18.7 0.85 18.7 0.83 17.8 0.67 16.0 0.44
750 12.8 0.36 13.7 0.42 15.5 0.56 17.0 0.68 18.4 0.84 19.5 0.98 20.1 1.05 20.0 1.23 19.1 0.85
800 13.5 0.42 14.4 0.49 16.1 0.63 17.5 0.77 18.9 0.93 20.1 1.0921.1 1.22 21.5 1.28 21.3 1.22
850 14.2 0.56 15.1 0.61 16.7 0.74 18.1 0.85 19.4 1.00 20.6 1.15 21.7 1.31 22.9 1.50 23.9 1.69
900 14.9 0.63 15.8 0.70 17.3 0.82 18.7 0.95 19.9 1.10 21.1 1.26 22.2 1.4223.3 1.62 24.4 1.80
950 15.7 0.72 16.5 0.78 17.9 0.91 19.3 1.06 20.5 1.21 21.7 1.37 22.8 1.55 23.8 1.7324.8 1.93
1000 16.4 0.81 17.2 0.88 18.6 1.02 19.9 1.18 21.1 1.34 22.2 1.50 23.3 1.69 24.3 1.86 25.22.06
1050 17.2 0.92 17.9 0.99 19.2 1.13 20.6 1.30 21.7 1.4822.8 1.64 23.8 1.83 24.92.01
25.7 2.21
1100 18.0 1.03 18.6 1.10 19.9 1.26 21.2 1.44 22.3 1.63 23.4 1.7924.4 1.98
25.4 2.18 26.3 2.38
1150 18.7 1.17 19.2 1.23 20.6 1.41 21.8 1.5823.0 1.7824.0 1.97
24.9 2.14 25.9 2.34 — —
1200 19.4 1.23 19.8 1.36 21.3 1.55 22.4 1.7223.6 1.92 24.62.12
25.5 2.29————
BkW — Fan Input kW x Motor Efficiency
kW — Kilowatt Input to Motor
50TFF008,009 (21.5 AND 24.3 kW)—STANDARD MOTOR (BELT DRIVE)
Airflow
(L/s)
External Static Pressure (Pa)
50 100 150 200 250 300 350 400 450 500
R/s kW R/s kW R/s kW R/s kW R/s kW R/s kW R/s kW R/s kW R/s kW R/s kW
800 7.0 0.27 9.0 0.45 9.6 0.53 11.0 0.70 12.0 1.86 13.1 1.03 13.9 1.25 15.0 1.74 15.5 1.96
16.6 2.45
900 7.5 0.37 9.3 0.55 10.1 0.66 11.4 0.84 12.3 1.02 13.4 1.19 14.2 1.43 15.3 1.86 15.82.10
16.8 2.55
1000 8.1 0.47 9.7 0.65 10.6 0.79 11.8 0.98 12.7 1.18 13.7 1.37 14.5 1.61 15.5 1.98
16.1 2.24 17.0 2.65
1100 8.7 0.57 10.1 0.75 11.1 0.92 12.2 1.12 13.1 1.34 14.0 1.55 14.8 1.79 15.7 2.10
16.4 2.38 17.2 2.75
1200 9.3 0.67 10.5 0.85 11.6 1.05 12.6 1.26 13.5 1.50 14.3 1.73 15.1 1.97
15.9 2.22 16.7 2.52 17.4 2.85
1300 9.8 0.80 11.0 0.99 12.1 1.21 13.0 1.43 13.9 1.67 14.7 1.93
15.5 2.18 16.2 2.34 16.9 2.69 17.6 2.97
1400 10.4 0.94 11.5 1.13 12.6 1.38 13.5 1.63 14.3 1.87
15.1 2.13 15.9 2.41 16.6 2.66 17.3 2.92 — —
1500 11.0 1.11 12.0 1.31 13.0 1.58 13.9 1.85 14.7 2.11
15.5 2.36 16.3 2.64 17.0 2.91————
BkW — Fan Input kW x Motor Efficiency
kW — Kilowatt Input to Motor
Performance data (cont)