FAN PERFORMANCE (SI) — VERTICAL DISCHARGE UNITS (cont)
LEGEND
NOTES:
1. Boldface indicates field-supplied drive required (see Note 3).
2. indicates field-supplied motor and drive required.
3. Factory-shipped drive range is 11.50 to 15.00 r/s. Other r/s’s may
require a field-supplied drive.
4. Values include losses for filters, unit casing, and wet coils.
5. Extensive motor and electrical testing on these units ensures that
the full range of the motor can be utilized with confidence. Using
your fan motors up to the kW ratings shown will not result in
nuisance tripping or premature motor failure. Unit warranty will not
be affected. See Evaporator-Fan Motor Performance table on
page 30 or additional information.
6. Use of a field-supplied motor may affect wire sizing. Contact your
Carrier representative to verify.
7. To convert kW to bkW:
BkW = kW x Motor Efficiency
Motor Efficiency: .83 Maximum Continuous kW: 2.12
8. Interpolation is permissible. Do not extrapolate.
9. Static pressure losses (i.e., economizer, electric heater) must be
added to external static pressure before entering Fan Performance
table.
LEGEND
NOTES:
1. Boldface indicates field-supplied drive required (see Note 3).
2. indicates field-supplied motor and drive required.
3. Factory-shipped drive range is 11.83 to 14.83 r/s. Other r/s’s may
require a field-supplied drive.
4. Values include losses for filters, unit casing, and wet coils.
5. Extensive motor and electrical testing on these units ensures that
the full range of the motor can be utilized with confidence. Using
your fan motors up to the kW ratings shown will not result in
nuisance tripping or premature motor failure. Unit warranty will not
be affected. See Evaporator-Fan Motor Performance table on
page 30 or additional information.
6. Use of a field-supplied motor may affect wire sizing. Contact your
Carrier representative to verify.
7. To convert kW to bkW:
BkW = kW x Motor Efficiency
Motor Efficiency: .85 Maximum Continuous kW: 3.31
8. Interpolation is permissible. Do not extrapolate.
9. Static pressure losses (i.e., economizer, electric heater) must be
added to external static pressure before entering Fan Performance
table.
50TFF012 (29.2 kW)—STANDARD MOTOR (BELT DRIVE)
Airflow
(L/s)
External Static Pressure (Pa)
50 100 150 200 250 300 350 400 450 500
R/s kW R/s kW R/s kW R/s kW R/s kW R/s kW R/s kW R/s kW R/s kW R/s kW
1100 7.6 0.36 9.2 0.46 10.2 0.56 11.3 0.70 12.7 0.74 12.9 0.80 13.6 0.90 14.4 1.09 15.2 1.2016.2 1.37
1200 7.9 0.39 9.3 0.51 10.4 0.63 11.4 0.75 12.8 0.86 13.0 0.90 13.9 1.02 14.6 1.13 15.4 1.38 16.3 1.60
1250 8.2 0.429.5 0.55 10.6 0.69 11.5 0.80 12.9 1.92 13.1 1.02 14.2 1.14 14.8 1.38 15.6 1.6516.5 1.83
1300 8.4 0.569.6 0.78 10.8 0.88 11.7 0.96 12.6 1.09 13.3 1.18 14.3 1.34 15.1 1.58 15.9 1.8116.7 2.03
1400 8.8 0.66 10.0 0.86 11.1 0.98 12.0 1.10 12.9 1.22 13.7 1.33 14.5 1.47 15.4 1.6716.2 1.9016.82.12
1500 9.2 0.74 10.4 0.95 11.5 1.09 12.4 1.23 13.2 1.35 14.0 1.49 14.8 1.57 15.6 1.77 16.4 1.97
17.1 2.21
1600 9.7 0.85 10.8 1.07 11.8 1.22 12.8 1.37 13.6 1.49 14.4 1.65 15.1 1.79 15.8 1.9416.5 2.09
17.3 2.31
1700 10.2 0.96 11.2 1.19 12.2 1.35 13.1 1.51 13.9 1.66 14.7 1.81 15.4 1.98
16.1 2.13 16.7 2.29 17.4 2.46
1800 10.6 1.09 11.7 1.34 12.6 1.51 13.5 1.67 14.3 1.85 15.0 2.01
15.7 2.18 16.4 2.36 17.1 2.54 17.7 2.71
1900 11.1 1.24 12.1 1.49 13.0 1.67 13.9 1.86 14.7 2.04
15.4 2.23 16.1 2.40 16.8 2.59 17.4 2.80 18.0 2.99
BkW Fan Input kW x Motor Efficiency
kW Kilowatt Input to Motor
50TFF014 (35.9 kW)—STANDARD MOTOR (BELT DRIVE)
Airflow
(L/s)
External Static Pressure (Pa)
50 100 150 200 250 300 350 400 450 500
R/s kW R/s kW R/s kW R/s kW R/s kW R/s kW R/s kW R/s kW R/s kW R/s kW
1500 9.7 0.66 10.8 0.84 11.7 0.91 12.6 1.09 13.5 1.27 14.3 1.32 15.11.4416.0 1.55 16.9 1.66 17.5 1.88
1550 9.9 0.72 11.0 0.89 11.9 1.01 12.8 1.15 13.7 1.34 14.5 1.46 15.2 1.38 16.1 1.71 17.0 1.79 17.5 2.02
1600 10.2 0.78 11.2 0.95 12.1 1.10 13.0 1.22 13.8 1.41 14.6 1.58 15.41.7116.2 1.79 17.0 1.92 17.62.15
1650 10.4 0.85 11.5 1.01 12.4 1.20 13.2 1.29 14.0 1.48 14.8 1.67 15.5 1.76 16.3 1.89 17.1 2.06 17.62.28
1700 10.7 0.91 11.7 1.08 12.6 1.29 13.4 1.38 14.2 1.55 15.0 1.76 15.7 1.92 16.4 2.01 17.1 2.18 17.7 2.36
1750 10.9 1.07 11.9 1.22 12.8 1.37 13.6 1.52 14.4 1.67 15.1 1.86 15.82.02 16.5 2.20 17.22.36 17.7 2.51
1800 11.1 1.12 12.1 1.29 13.0 1.45 13.8 1.60 14.6 1.75 15.3 1.9516.0 2.12 16.7 2.29 17.32.47 17.92.64
1850 11.4 1.19 12.4 1.36 13.2 1.54 14.0 1.69 14.7 1.84 15.5 2.03 16.22.22 16.82.40 17.5 2.59 18.1 2.77
1900 11.6 1.26 12.6 1.45 13.4 1.62 14.2 1.78 14.9 1.93 15.62.12 16.32.33 17.0 2.52 17.7 2.71 18.32.90
1950 11.9 1.34 12.8 1.53 13.7 1.71 14.4 1.88 15.1 2.03 15.82.22 16.5 2.44 17.22.64 17.82.83 18.4 3.03
2000 12.1 1.42 13.0 1.62 13.9 1.80 14.6 1.99 15.32.15 16.0 2.32 16.7 2.54 17.32.76 18.0 2.96 18.63.16
2050 12.4 1.51 13.2 1.71 14.1 1.89 14.8 2.09 15.5 2.26 16.22.42 16.92.64 17.5 2.88 18.1 3.09 17.7 3.30
2100 12.6 1.60 13.5 1.81 14.3 2.00 15.0 2.21 15.7 2.39 16.4 2.54 17.0 2.76 17.7 3.01 18.33.23
18.9 3.44
2150 12.8 1.70 13.7 1.92 14.5 2.12 15.32.33 15.92.51 16.62.68 17.22.88 17.83.14
18.5 3.36 19.1 3.59
2200 13.1 1.79 13.9 2.02 14.7 2.22 15.5 2.45 16.1 2.6416.82.82 17.4 3.01 18.0 3.25
18.6 3.51 19.2 3.75
2250 13.3 1.91 14.2 2.14 15.0 2.34 15.7 2.57 16.4 2.77 17.0 2.97 17.63.14
18.2 3.39 18.8 3.65 19.4 3.90
2300 13.6 2.01 14.4 2.26 15.22.47 15.92.69 16.62.92 17.23.12 17.83.30
18.4 3.52 19.0 3.80 19.5 4.06
2350 13.8 2.13 14.6 2.38 15.4 2.6016.1 2.82 16.83.07 17.4 3.26
18.0 3.47 18.6 3.67 19.2 3.93 19.7 4.22
BkW Fan Input kW x Motor Efficiency
kW Kilowatt Input to Motor