EasyManua.ls Logo

Carrier 50TFF007-014 - EVAPORATOR-FAN MOTOR PERFORMANCE; FAN R;S AT MOTOR PULLEY SETTINGS* (SI); FAN RPM AT MOTOR PULLEY SETTINGS* (ENGLISH)

Carrier 50TFF007-014
44 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
30
EVAPORATOR-FAN MOTOR PERFORMANCE
LEGEND *Extensive motor and electrical testing on these units ensures that the
full range of the motors can be utilized with confidence. Using your fan
motors up to the ratings shown in this table will not result in nuisance
tripping or premature motor failure. Unit warranty will not be affected.
FAN R/s AT MOTOR PULLEY SETTINGS* (SI)
*Approximate fan r/s shown.
FAN RPM AT MOTOR PULLEY SETTINGS* (ENGLISH)
*Approximate fan rpm shown.
UNIT
50TFF
UNIT RATED
VOLTAGE
MAXIMUM
ACCEPTABLE
CONTINUOUS
BkW*
MAXIMUM
ACCEPTABLE
CONTINUOUS
BHP*
MAXIMUM
ACCEPTABLE
OPERATING
WATTS
MAXIMUM
AMP DRAW
007 400 1.79 2.40 2,120 3.0
008 400 1.79 2.40 2,120 3.0
009 400 1.79 2.40 2,120 3.0
012 400 1.79 2.40 2,120 3.0
014 400 2.76 3.70 3,313 5.5
Bhp Brake Horsepower
BkW kW x Motor Efficiency
UNIT 50TFF
MOTOR PULLEY TURNSOPEN
0
1
/
2
11
1
/
2
22
1
/
2
33
1
/
2
44
1
/
2
5
007 20.08 19.67 19.17 18.75 18.25 17.83 17.33 16.92 16.42 16.00 15.50
008,009 14.67 14.25 13.83 13.33 12.92 12.50 12.08 11.67 11.25 10.83 10.33
012 15.00 14.58 14.25 13.92 13.58 13.25 12.92 12.58 12.25 11.92 11.50
014 14.83 14.58 14.25 13.72 13.67 13.33 13.08 12.75 12.50 12.17 11.83
UNIT
50TFF
MOTOR PULLEY TURNSOPEN
0
1
/
2
11
1
/
2
22
1
/
2
33
1
/
2
44
1
/
2
5
007 1205 1180 1150 1125 1095 1070 1040 1015 985 960 930
008,009 880 855 830 800 775 750 725 700 675 650 620
012 900 875 855 835 815 795 775 755 735 715 690
014 890 875 855 835 820 800 785 765 750 730 710