A Open
B Closed
C Open
D Closed
LEGEND
LCS Loss of Charge Switch
] Acutrol Metering Device
r_ Check Valve indicates direction of
(Arrow flow)
HEATING CYCLE
1. Hot gas from compressor flows through the 4-way valve and is
directed to the cooling liquid line check valve. It is then condensed
and directed through subcooling circuits and out to the strainer
and the check valve in the heating liquid line.
2. The refrigerant then feeds the outdoor coil through the Acutrol
metering device on each circuit.
3. Each circuit evaporates the refrigerant and the circuits are com-
bined in the outdoor header with some of the circuits flowing th rough
the check valve.
4. The refrigerant then flows through the 4-way valve, accumulator,
and back to the compressor.
Fig. 25-Typical Heat Pump Operation, Heating Mode
C95045