Base unit dimensions — 50ZH060
REQUIRED CLEARANCES TO COMBUSTIBLE MAT’L
Millimeters (in.)
Top of Unit ...................................0
Bottom of Unit .................................0
Side of Unit with Duct Openings ......................0
Side of Unit Opposite Duct Openings ...................0
NEC REQUIRED CLEARANCES
Millimeters (in.)
Between Units, Power Entry Side .................1066.8 (42.00)
Unit and Ungrounded Surfaces, Power Entry Side ....... 914.0 (36.00)
Unit and Block or Concrete Walls and Other Grounded
Surfaces, Power Entry Side ....................1066.8 (42.00)
REQUIRED CLEARANCES FOR SERVICING
Millimeters (in.)
Top of Unit ................................914.0 (36.00)
Side of Unit Opposite Duct Openings ................762.0 (30.00)
Side of Unit with Power Entry ....................762.0 (30.00)
(Except for NEC Requirements)
LEGEND
NEC — National Electrical Code
NOTES:
1. Clearances must be maintained to prevent recirculation of air from outdoor-
fan discharge. A removable fence or barricade requires no clearance.
2. Dimensions are in millimeters. Dimensions in [ ] are in inches.
3. is the center of gravity.
UNIT
ELECTRICAL
CHARACTERISTICS
V-Ph-Hz
UNIT WEIGHT CENTER OF GRAVITY mm (in.)
Lb Kg X Y Z
50ZH060
208/230-1-60, 208/230-3-60,
460-3-60
368 167 356 (14.00) 508 (20.00) 406 (16.00)
7