17. CONNECTING CONDENSATE DRAIN LINE
17-1 SIZE OF CONDENSATE DRAIN LINE
The condensate drain line (not supplied) for indoor unit must be made of PVC piping with an inside
diameter of 5/8” (16 mm) and have suitable length for the chosen installation site.
17-2 POSSIBLE OUTLET LOCATIONS OF CONDENSATE DRAIN LINE WITH
REFRIGERANT PIPING LINES AND ELECTRICAL CABLES FROM THE INDOOR UNIT
NOTES
1. For the left-hand and right-hand
piping, remove the pipe cover from
the side panel.
2. Explain to the clients that the pipe
cover must be kept as it may be used
when relocate the air conditioner to
any other place
Back right
condensate drain line
Back left
condensate drain line
Right side
condensate drain line
Left side
condensate drain line
1
2
3
4