Table 14–Tabulated Data Based On 21,000 Btuh High-Heat/14,500 Btuh for Low-Heat Per Burner,
Derated 4 Percent For Each 1000 Ft Above Sea Level
ALTITUDE
RANGE
(FT)
AVG GAS
HEAT VALUE
AT ALTITUDE
(BTU/CU FT)
SPECIFIC GRAVITY OF NATURAL GAS
0.58 0.60 0.62 0.64
Orifice
No.
Manifold
Pressure
Orifice
No.
Manifold
Pressure
Orifice
No.
Manifold
Pressure
Orifice
No.
Manifold
Pressure
U.S.A. Only
5001
to
6000
725 44 3.5/1.7 43 3.2/1.5 43 3.3/1.6 43 3.4/1.6
750 44 3.3/1.6 44 3.4/1.6 44 3.5/1.7 43 3.2/1.5
775 45 3.7/1.8 44 3.2/1.5 44 3.3/1.6 44 3.4/1.6
800 46 3.7/1.8 46 3.8/1.8 45 3.8/1.8 44 3.2/1.5
825 46 3.5/1.7 46 3.6/1.7 46 3.7/1.8 46 3.8/1.8
850 47 3.7/1.8 47 3.8/1.8 46 3.5/1.7 46 3.6/1.7
875 47 3.5/1.7 47 3.6/1.7 47 3.7/1.8 46 3.4/1.6
900 48 3.8/1.8 47 3.4/1.6 47 3.5/1.7 47 3.7/1.7
ALTITUDE
RANGE
(FT)
AVG GAS
HEAT VALUE
AT ALTITUDE
(BTU/CU FT)
SPECIFIC GRAVITY OF NATURAL GAS
0.58 0.60 0.62 0.64
Orifice
No.
Manifold
Pressure
Orifice
No.
Manifold
Pressure
Orifice
No.
Manifold
Pressure
Orifice
No.
Manifold
Pressure
U.S.A. Only
6001
to
7000
675 44 3.5/1.7 43 3.2/1.5 43 3.3/1.6 43 3.4/1.6
700 44 3.3/1.6 44 3.4/1.6 44 3.5/1.7 43 3.2/1.5
725 45 3.7/1.8 45 3.8/1.8 44 3.3/1.6 44 3.4/1.6
750 46 3.6/1.7 46 3.8/1.8 45 3.7/1.8 45 3.8/1.8
775 46 3.4/1.6 46 3.5/1.7 46 3.6/1.7 46 3.8/1.8
800 47 3.6/1.7 47 3.8/1.8 46 3.4/1.6 46 3.5/1.7
825 47 3.4/1.6 47 3.5/1.7 47 3.6/1.7 47 3.8/1.8
850 48 3.7/1.7 48 3.8/1.8 47 3.4/1.6 47 3.5/1.7
ALTITUDE
RANGE
(FT)
AVG GAS
HEAT VALUE
AT ALTITUDE
(BTU/CU FT)
SPECIFIC GRAVITY OF NATURAL GAS
0.58 0.60 0.62 0.64
Orifice
No.
Manifold
Pressure
Orifice
No.
Manifold
Pressure
Orifice
No.
Manifold
Pressure
Orifice
No.
Manifold
Pressure
U.S.A. Only
7001
to
8000
650 44 3.3/1.6 44 3.4/1.6 44 3.5/1.7 43 3.2/1.5
675 45 3.7/1.8 45 3.8/1.8 44 3.3/1.6 44 3.4/1.6
700 46 3.6/1.7 46 3.7/1.8 46 3.8/1.8 45 3.8/1.8
725 47 3.8/1.8 46 3.5/1.7 46 3.6/1.7 46 3.7/1.8
750 47 3.5/1.7 47 3.7/1.8 47 3.8/1.8 46 3.5/1.6
775 48 3.8/1.8 47 3.4/1.6 47 3.6/1.7 47 3.7/1.7
800 48 3.6/1.7 48 3.7/1.8 48 3.8/1.8 47 3.4/1.6
825 48 3.3/1.6 48 3.5/1.6 48 3.6/1.7 48 3.7/1.8
ALTITUDE
RANGE
(FT)
AVG GAS
HEAT VALUE
AT ALTITUDE
(BTU/CU FT)
SPECIFIC GRAVITY OF NATURAL GAS
0.58 0.60 0.62 0.64
Orifice
No.
Manifold
Pressure
Orifice
No.
Manifold
Pressure
Orifice
No.
Manifold
Pressure
Orifice
No.
Manifold
Pressure
U.S.A. Only
8001
to
9000
625 45 3.7/1.8 45 3.8/1.8 44 3.3/1.6 44 3.4/1.6
650 46 3.6/1.7 46 3.7/1.8 46 3.8/1.8 45 3.8/1.8
675 47 3.8/1.8 46 3.4/1.6 46 3.5/1.7 46 3.7/1.7
700 47 3.5/1.7 47 3.6/1.7 47 3.7/1.8 46 3.4/1.6
725 48 3.7/1.8 48 3.8/1.8 47 3.5/1.7 47 3.6/1.7
750 48 3.5/1.7 48 3.6/1.7 48 3.7/1.8 48 3.8/1.8
775 49 3.8/1.8 48 3.4/1.6 48 3.5/1.7 48 3.6/1.7
* Orifice numbers 43 are factory installed