TYPICAL WIRING SCHEMATIC
A95236
ELECTRICAL DATA
UNIT SIZE
VOLTS HERTZ
PHASE
OPERATING
VOLTAGE RANGE
MAXIMUM
UNIT AMPS
MAXIMUM
WIRE
LENGTH
FT (M)‡
MAXIMUM
FUSE OR CKT
BKR AMPS†
MINIMUM
WIRE GAGE
Maximum* Minimum*
070-12 115-60-1 127 104 9.0 30 (9.1) 15 14
090-16 115-60-1 127 104 9.6 29 (8.8) 15 14
110-20 115-60-1 127 104 15.1 29 (8.8) 20 12
135-22 115-60-1 127 104 14.9 30 (9.1) 20 12
155-22 115-60-1 127 104 15.0 29 (8.8) 20 12
* Permissible limits of the voltage range at which unit operates satisfactorily.
Time---delay type is recommended.
Length shown is as measured on e way along wire path between un it and service panel for maximum 2 percent voltage drop.
58CVA/CVX