EasyManua.ls Logo

Carrier 58DH - Venting

Carrier 58DH
8 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Place
a
ground
joint
union
between
the
gas
control
manifold
and
the
manual
gas
shutoff
valve.
See
Fig.
4.
A
WARNING
Use
the
proper
length
of
pipes
to
avoid
stress
on
the
gas
control
manifold.
Protect
all
segments
of
the
piping
system
against
physical
and
thermal
damage.
Support
all
piping
with
appropriate
straps,
hangers,
etc.
Use
a
minimum
of
one
hanger
every
6
feet.
For
pipe
sizes
larger
than
1/2
in.,
follow
recommendations
of
national
codes.
A
CAUTION
If
a
flexible
connector
is
required
or
allowed
by
the
authority
having
jurisdiction,
black
iron
pipe
shall
be
installed
at
the
gas
valve
and
extend
a
minimum
of
2
in.
outside
the
furnace
casing.
Piping
should
be
pressure
tested
in
accordance
with
local
and
national
plumbing
and
gas
codes
before
furnace
has
been
attached.
If
pressure
exceeds
0.5
psig(
14
in.
wg),
gas
supply
pipe
must
be
disconnected
from
furnace
before
pressure
test.
If
test
pressure
is
equal
to
or
less
than
0.5
psig
(14
in.
wg),
close
manual
shutoff
valve
located
on
gas
valve
before
test.
Ground
joint
union
should
be
loosened
before
pressure
testing.
After
all
connections
have
been
made,
purge
the
lines
and
check
for
leakage.
_
A
WARNING
Never
purge
a
line
into
a
combustion
chamber.
Never
use
matches,
candles,
flame,
or
other
sources
of
ignition
for
the
purpose
of
checking
leakage.
Use
a
soap-and-water
solution
to
check
for
leakage.
VENTING
-+
Venting
Category
I
This
furnace
complies
with
Venting
Category
I,
as
noted
on
the
furnace
rating
plate.
This
refers
to
the
type
of
venting
system
as
specified
in
the
ANSI
21.47
requirements,
against
which
this
appliance
is
tested
and
design
certified
by
the
American
Gas
Associa¬
tion
Laboratories.
Specifically,
Venting
Category
1
is
a
nonpositive
venting
system,
meaning
the
static
pressure
in
the
vent
is
less
than
atmospheric
pressure,
and
the
stack
gas
temperature
is
at
least
140
degrees
F
above
the
dew
point
temperature.
Do
not
attempt
to
confirm
this
data
by
field
measurement,
as
specific
laboratory
equipment
and
test
conditions
are
required.
Consult
local
codes.
For
additional
information
refer
to
the
National
Fuel
Gas
Code
(NFPA
No.
54-1984
or
ANSI
Z223.1-1984).
Unless
the
local
codes
direct
other¬
wise,
unit
may
be
vented
to
an
NFPA-
or
ANSI-approved
chimney,
or
to
a
listed
type-Bl
gas
vent.
Connect
the
vent
collar
to
the
chimney
or
gas
vent
to
be
used.
Follow
these
recommendations:
1.
Select
flue
connection
material
that
is
satisfactory
for
installation
and
that
meets
requirements
of
local
codes.
2.
Flue
connection
pipe
must
be
at
least
as
large
as
outlet
collar
on
furnace.
No
reduction
in
this
size
is
permissible
in
pipe
run.
NOTE:
The
clearance
requirements
which
must
be
maintained
between
the
furnace
vent
pipe
and
com¬
bustible
materials
are
as
follows:
6
in.
for
single-wall
vent
and
one
in.
for
type-Bl
(double-wall)
vent.
When
B1
vent
material
is
used,
make
the
single
wall-
to-Bl
transition
with
a
listed
transition
fitting
directly
on
the
flue
collar
or
flue
extension
pipe.
3.
Run
pipe
as
directly
as
possible
with
minimum
number
of
turns
and
minimum
of
12
in.
straight
pipe
before
the
first
bend
(upflow
and
downflow).
4.
Maintain
minimum
of
1/4in.
per
linear
ft
upward
slope
on
all
horizontal
runs.
5.
Rigidly
support
flue
pipe
with
hangers
and
straps
to
ensure
that
there
will
be
no
movement
after
installation.
6.
Insert
smallest
flue
connection
pipe
at
highest
level
consistent
with
available
headroom
or
clearance
to
combustible
materials,
when
2
or
more
vent
con¬
nectors
enter
a
common
gas
vent
or
chimney
flue.
7.
Extend
flue
connection
pipe
through
chimney
wall
flush
with
inner
face
of
chimney
liner
and
above
extreme
bottom
to
avoid
restriction.
A
WARNING
Never
connect
into
a
chimney
serving
a
fireplace
unless
the
Fireplace
opening
is
sealed
off.
8.
No
portion
of
venting
system
shall
extend
into,
or
pass
through,
any
circulating
air
duct
or
plenum.
9.
Chimney
or
gas
vent
shall
extend
at
least
5
ft
above
highest
connected
draft
hood
and
should
extend
high
enough
above
roof
or
neighboring
obstruction,
so
that
wind
from
any
direction
will
not
create
positive
pressure
in
vicinity
of
chimney
or
gas
vent
outlet.
Chimney
or
gas
vent
should
extend
3
ft
higher
than
point
of
emergence
through
roof,
and
at
least
2
ft
higher
than
any
object
within
a
radius
of
10
feet.
See
Fig.
5.
10.
A
type-Bl
gas
vent
shall
terminate
above
roof
surface
with
a
listed
cap
or
roof
assembly.
Common
Venting
with
Other
Appliances
This
furnace
may
be
connected
to
a
common
chimney
or
listed
type-Bl
gas
vent
with
other
listed
gas-fired
appli¬
ances.
The
vent
system
of
this
induced-draft
furnace
operates
at
negative
pressure
during
normal
operation.
If
for
any
reason
the
pressure
in
the
vent
system
becomes
positive
(may
happen
if
chimney
is
inadvertently
blocked),
the
furnace
shuts
down
and
locks
off.
This
is
accomplished
by
means
of
draft
safeguard
switch
located
on
tube
attached
to
relief
box
just
above
draft
inducer
blower.
The
design
of
this
furnace,
equipped
with
draft
safeguard
switch,
has
been
tested
by
the
American
Gas
Association
Laboratories.
4

Other manuals for Carrier 58DH

Related product manuals