14
Typical wiring schematic
Electrical data
* Permissible limits of the voltage range at which unit operates satisfactorily.
Time-delay type is recommended.
Length shown is as measured 1 way along wire path between unit and service panel for maximum 2 percent voltage drop.
UNIT SIZE
VOLTS HERTZ-
PHASE
OPERATING
VOLTAGE RANGE
MAXIMUM
UNIT AMPS
MAXIMUM
WIRE
LENGTH (FT)‡
MAXIMUM
FUSE OR CKT
BKR AMPS†
MINIMUM
WIRE GAGE
Maximum* Minimum*
045-08 115-60-1 127 104 5.6 47 15 14
045-12 115-60-1 127 104 7.0 39 15 14
070-08 115-60-1 127 104 5.0 52 15 14
070-12 115-60-1 127 104 6.7 40 15 14
070-16 115-60-1 127 104 9.4 29 15 14
090-14 115-60-1 127 104 8.1 34 15 14
090-16 115-60-1 127 104 9.8 28 15 14
090-20 115-60-1 127 104 13.6 32 20 12
110-12 115-60-1 127 104 8.1 34 15 14
110-16 115-60-1 127 104 10.0 28 15 14
110-22 115-60-1 127 104 13.6 32 20 12
135-16 115-60-1 127 104 10.0 28 15 14
135-22 115-60-1 127 104 14.4 30 20 12
155-20 115-60-1 127 104 15.0 29 20 12
115-V FIELD-
SUPPLIED
DISCONNECT
AUXILIARY
J-BOX
24-V
TERMINAL
BLOCK
THREE-WIRE
HEATING-ONLY
FIVE WIRE
NOTE 1
NOTE 2
FIELD-SUPPLIED
DISCONNECT
CONDENSING
UNIT
TWO
WIRE
FURNACE
C
O
N
T
R
O
L
R
G
COM
WCR GY
GND
GND
FIELD 24-V WIRING
FIELD 115-, 208/230-, 460-V WIRING
FACTORY 24-V WIRING
FACTORY 115-V WIRING
208/230- OR
460-V
THREE
PHASE
208/230-V
SINGLE
PHASE
BLOWER DOOR SWITCH
WHT
BLK
WHT
BLK
NOTES: Connect Y-terminal in furnace as shown for proper blower operation.
Some thermostats require a "C" terminal connection as shown.
If any of the original wire, as supplied, must be replaced, use
same type or equivalent wire.
W
Y/Y2
GND
THERMOSTAT
TERMINALS
1.
2.
3.
A99440