Step 2—24-v Wiring
Make field 24-v thermostat connections at 24-v terminal block on
control center. For proper cooling operation, Y wire from thermo-
stat MUST be connected to Y terminal on control center, as shown
in Fig. 22. The 24-v terminal board is marked for easy connection
of field wiring. (See Fig. 24.) The 24-v circuit contains a 3-amp,
automotive-type fuse located on control center. (See Fig. 25.) Any
electrical shorts of 24-v wiring during installation, service, or
maintenance may cause fuse to blow. If fuse replacement is
required, use only a fuse of identical size (3 amp).
NOTE: Use AWG No. 18 color-coded copper thermostat wire for
lengths up to 100 ft. For wire lengths over 100 ft, use AWG No.
16 wire.
Table 3—Electrical Data
UNIT
SIZE
VOLTS—
HERTZ—
PHASE
OPERATING
VOLTAGE RANGE
MAX
UNIT
AMPS
UNIT
AMPACITY†
MIN
WIRE
SIZE
MAX WIRE
LENGTH (FT)‡
MAX FUSE OR
CKT BKR AMPS**
Max* Min*
040-08 115—60—1 127 104 6.1 8.4 14 44 15
040-12 115—60—1 127 104 7.3 10.0 14 37 15
060-08 115—60—1 127 104 6.1 8.4 14 44 15
060-12 115—60—1 127 104 7.1 9.8 14 38 15
060-16 115—60—1 127 104 9.5 12.8 14 29 15
080-12 115—60—1 127 104 7.6 10.4 14 36 15
080-16 115—60—1 127 104 10.0 13.4 14 28 15
080-20 115—60—1 127 104 14.1 18.4 12 31 20
100-16 115—60—1 127 104 10.2 13.5 14 27 15
100-20 115—60—1 127 104 14.8 19.3 12 30 20
120-20 115—60—1 127 104 14.6 19.1 12 30 20
* Permissible limits of voltage range at which unit will operate satisfactorily.
Unit ampacity = 125 percent of largest operating component’s full load amps plus 100 percent of all other potential operating components’ (EAC, humidifier, etc.) full
load amps.
Length shown is as measured 1 way along wire path between unit and service panel for maximum 2 percent voltage drop.
** Time-delay fuse is recommended.
Fig. 25—Control Center
A93052
G
R
Y
W
3-AMP FUSE
Com
24V
HUMIDIFIER TERMINAL
(24-VAC 0.5 AMP MAX)
LED OPERATION &
DIAGNOSTIC LIGHT
HARNESS CONNECTOR
24V TRANSFORMER SEC-2
SPARE 1
SPARE 2
EAC 1 (BLACK)
EAC-ELECTRONIC AIR CLEANER
TERMINALS (115-VAC 1.5 AMP MAX)
EAC 2 (WHITE)
115-VAC (L2) NEUTRAL
CONNECTION
24V THERMOSTAT
TERMINALS
BLOWER SPEED
SELECTION TERMINALS
INDUCER MOTOR
CONNECTOR
115-VAC (L1)
POWER
SUPPLY
HOT SURFACE
IGNITOR
CONNECTOR
HEAT
COOL
BLOWER OFF DELAY
ADJUSTMENT SWITCH
SEC-1
TEST/TWIN
HUM
19