HEATING
ft
COOLING
58ED,PB
Horizontal
Gas-Fired
Furnaces
All
forced
air
furnaces
are
equipped
with
a
high
temperature
limit
switch
which
prevents
the
furnace
from
overheating.
If
the
furnace
overheats
for
any
reason,
the
high
temperature
limit
opens,
breaking
the
circuit
to
the
gas
valve.
The
blower
motor
continues
to
run.
The
main
burners
cycle
on
limit
until
the
fault
is
corrected.
A
WARNING
If
overheating
occurs,
or
if
the
gas
supply
fails
to
shut
off,
shut
off
the
manual
gas
valve
to
the
furnace
before
shutting
off
the
electrical
supply.
The
furnace
is
equipped
with
either
Honeywell
S86E
or
S86G
intermittent
pilot
control.
S86E
control.
If
the
pilot
fails
to
light,
the
pilot
valve
and
spark
gap
remain
energized
until
there
is
a
successful
ignition.
S86G
control:
If
the
pilot
fails
to
light,
the
control
will
shut
down
the
system.
To
initiate
a
reignition
trial,
turn
down
the
thermostat
to
lowest
setting,
wait
at
least
60
seconds,
and
then
reset
thermostat
to
a
setting
above
room
temperature.
Starting
Procedure
STANDING
PILOT
MODELS
1.
Set
the
manual
gas
shutoff
valve
at
OFF
position.
Wait
5
minutes.
2.
Be
sure
all
electrical
power
to
furnace
is
off.
3
Check
all
wiring
using
proper
wiring
diagram
on
inside
of
blower
door.
4.
Light
the
pilot
by
following
instructions
on
lighting
plate.
(Main
burners
should
not
light.)
a)
Remove
burner
cover.
b)
Turn
manual
gas
shutoff
valve
to
PILOT
position.
c)
Depress
dial,
light
pilot
with
a
match
or
taper.
Keep
dial
depressed
until
pilot
remains
lit
after
dial
is
released
(approximately
30-45
seconds).
If
pilot
does
not
remain
lit,
repeat
operation,
allowing
a
longer
period
before
releasing
dial.
d)
Replace
burner
cover.
5.
Adjust
pilot
flame
to
envelop
the
thermocouple
a
distance
of
3/8
to
1/2
inch.
The
adjusting
screw
for
pilot
flame
is
located
on
main
gas
control.
With
standing
pilot,
rate
is
approximately
1000
Btuh.
See
Fig.
13.
Fig.
13
Pilot
Thermocouple
or
Sensor
Position
6.
With
the
pilot
lit,
set
thermostat
above
room
temperature.
7.
Turn
on
power
supply
to
furnace.
This
energizes
gas
valve
which
should
click
open.
The
burners
should
not
light.
8.
Open
the
manual
gas
valve
on
the
automatic
gas
valve.
Burners
should
light
and
remain
on.
9.
Check
for
leaks
in
manual
valve,
gas
control
valve
and
gas
connections
using
soap
and
water
solution.
A
CAUTION
Never
use
an
open
flame
when
testing
for
leaks.
Use
soap
and
water
solution.
10.
L
eave
burners
on
for
15
minutes
before
making
combustion
adjustment
ELECTRONIC
IGNITION
MODELS
1.
Set
the
manual
gas
shutoff
valve
at
OFF
position.
Wait
5
minutes.
2.
Be
sure
all
electrical
power
to
furnace
is
off
3
Check
all
wiring
using
proper
wiring
diagram
on
inside
of
blower
door.
4
Set
thermostat
above
room
temperature.
5.
Turn
on
power
supply
to
furnace.
This
energizes
the
pilot
valve
and
spark
igniter.
The
burners
should
not
light.
6.
Turn
dial
on
gas
valve
to
ON
position.
The
pilot
should
light.
When
the
sensing
probe
detects
the
presence
of
pilot
flame,
the
control
de-energizes
spark
igniter
and
energizes
main
gas
valve.
Main
burners
should
light
and
remain
on.
(If
system
shuts
down
on
S86G
control,
a
reignition
trial
is
necessary.)
7.
Check
for
leaks
in
manual
valve,
gas
control
valve
and
gas
connections
using
a
soap
and
water
solution.
A
CAUTION
Never
use
an
open
flame
when
testing
for
gas
leaks.
Use
a
soap
and
water
solution.
8
Leave
burners
on
for
15
minutes
before
making
a
combustion
adjustment.
Combustion
Adjustment
ALL
FURNACES
A
primary
air
shutter
assembly
is
provided
on
all
furnaces.
The
shutters
are
factory
set
for
natural
gas
furnaces
and
a
closed
position
for
LP
gas
furnaces.
Readjustment
may
be
required
to
obtain
optimum
setting.
Shutters
are
individual
to
each
burner,
so
adjustment
of
the
burner
flame
must
be
done
one
burner
at
a
time.
See
Fig.
14.
Loosen
the
locking
screw
and
close
the
air
shutter.
This
should
cause
the
burner
flame
to
glow
bright
yellow
Open
the
shutter
until
the
flame
turns
blue.
Lock
the
locking
screw.
See
Fig.
15
for
proper
flame.
Repeat
this
procedure
until
all
burners
are
properly
adjusted.
A
visual
check
of
the
main
burner
and
pilot
flame
should
be
made
at
the
beginning
of
each
heating
season.
Safety
Pilot
Check
For
Standing
Pilot
Models
Only.
After
operating
for
15
minutes,
turn
the
valve
to
the
OFF
position.
The
pilot
switch
should
snap
open
between
20
seconds
and
3
minutes
later.
To
re-ignite
pilot,
follow
the
nameplate
instructions.
Manufacturer
reserves
the
right
to
discontinue,
or
change
at
any
time,
specifications
or
designs
without
notice
and
without
incurring
obligations.