EasyManua.ls Logo

Carrier 59SC2A - Page 56

Carrier 59SC2A
84 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
59SC2A
VENT
TERMINAL
OX)
AIR
SUPPLY
INLET
AREA
WHERE
TERMINAL
IS
NOT
PERMITED
A12326
NOTE:
The
following
is
based
upon
National
codes
for
gas
appliances
and
is
provided
as
a
reference.
Refer
to
local
codes
which
may
supersede
these
standards
and/or
recommendations.
it
cl
Descrinti
Canadian
Installations
1)
U.S.
Installations
*)
em
earance
eseription
(per
CAN/CSA
B149.1)
(per
ANSI
2223.1/NFPA
54)
Clearance
above
grade,
veranda,
porch, deck,
balcony
12
in.
(805
mm)
.
A
or
anticipated
snow
level 18
in.
(457
mm)
above
roof
surface.
12
in.
(805
mm)
12
in.
(805
mm)
for
appliances
>10,000
Btuh
(3
kW)
9 in.
(229
mm)
for
appliances
>10,000
Btuh
(3
kW)
B
Clearance
to
a
window
or
door
that
may
be
opened
and
</=100,000
Btuh
(
30
kW),
and
</=
50,000
Btuh
(
15
kW),
36
in.
(914
mm)
for
appliances
>100,000
Btuh
(30
kW)
12
in.
(805
mm)
for
appliances
>50,000
Btuh
(15kW)
Cc
Clearance
to
a
permanently
closed
window
Vertical
clearance
to
a
ventilated
soffit
located
above
ao.
; ;
D
the
terminal
within
a
horizontal
distance
of
2
feet
(61
For
clearances
not
specified
in
ANSI
2223.1/NFPA
54
or
CAN/CSA
B149.1,
clearances
shall
be
in
accordance
with
local
cm}
from
the
centerline
of
the
terminal
installation
codes
and
the
requirements
of
the
gas supplier
and
the
manufacturer’s
installation
instructions.
E
Clearance
fo
an
unventilated
soffit
Manufacturer's
Recommendation:
See
Notes
3-8.
F
Clearance
to
an
outside
corner
G
Clearance
to
an
inside
corner
H
Clearance
to
each
side
of
the
centerline
extended
above
3
ft.
(.9
M)
within
15
ft.
(4.6
M)
3
ft.
(.9
M)
within
15
ft.
(4.6
M)
electrical
meter
or
gas
service
regulator
assembly
above
the
meter/regulator
assembly.
above
the
meter/regulator
assembly.
I
Clearance
to
service
regulator
vent
outlet
Sft.
(9
M)
See
Note
4.
_
ve
.
ou
12
in.
(805
mm)
for
appliances
>10,000
Btuh(3
kW)
9 in.
(9
mm)
for
appliances
>10,000
Btuh
(3
kW)
J
Clearance
conbuaton
ait
Tet
to
any
cher
spplanes
and
</=
100,000
Btuh
(
30
kiN,
and
</=
50,000
Btuh
(15
kW),
36
in.
(914
mm)
for
appliances
>100,000
Btuh
(30
kW)
12
in.(305
mm)
for
appliances
>50,000
Btuh
(15kW)
K
Clearance
to
a
mechanical
air
supply
inlet
6
ft.
(1.8
M)
Sft.
(9
M)
12
in.
(805
mm).
See
Note
4.
L
Clearance
under
a
veranda,
porch, deck,
or
balcony
Permitted
only
if
veranda,
porch, deck,
or
balcony
is
fully
open
on
a
minimum
of
two
sides
beneath
the
floor.
Manufacturer's
Recommendation:
See
Notes
3-8.
Clearance
to
each
side
of
the
centerline
extended
above
M
or
below
vent
terminal
of
the
furnace
toa
dryer
or
water
12
in.
(905
mm)
12
in.
(905
mm)
heater
vent,
or
other
appliance’s
direct
vent
intake
or
exhaust
N
Inlet
air
clearance
to
a
moisture
exhaust
duct
3
ft.
(9
M)
3
ft.
(9
M)
(dryer
vent,
spa
exhaust,
etc.)
0
Clearance
from
a
plumbing
vent
stack
3
ft.
(9
M)
3
ft.
(9
M)
7
ft.
(2.1
M)
See
Note
4
p
Clearance
above paved
sidewalk
or
paved
driveway
Vent
shall
not
terminate
above
a
sidewalk
or
paved
driveway
that
is
ee
Note
*
located
on
public
property
located
between
two
single
alin
and
serves
both
Manufacturers
Recommendation:
See
Notes
3-8.
>
greater
than, =
greater
than
or
equal
to,
<
less
than, <
less
than
or
equal
to
Notes:
In
accordance
with
the
current
CAN/CSA
B149.1,
Natural
Gas
and
Propane
Installation
Code.
In
accordance
with
the
current
ANSI
Z223.1/NFPA
54,
National
Fuel
Gas
Code
NOTE:
This
table
is
based
upon
National
codes
for
gas
appliances, and
are
provided
as
a
reference.
Refer
to
Local
codes
which
may
supersede
these
standards
and/or
recommendations.
of
the
gas
supplier
and
the
manufacturer's
installation
instructions.
For
clearances
not
specified
in
ANS]
Z223.1/NFPA
54
or
CAN/CSA
B
149.1,
clearances
shall
be
in
accordance
with
local
installation
codes
and
the
requirements
When
locating
vent
terminations,
consideration
must
be
given
to
prevailing
winds,
location,
and
other
conditions
which
may
cause
recirculation
of
the
combustion
products
of
adjacent
vents.
Recirculation
can
cause
poor
combustion,
inlet
condensate
problems,
and
accelerated
corrosion
of
the
heat
exchangers.
Design
and
position
vent
outlets
to
avoid
ice
build-up
on
and
moisture
damage
to
surrounding
surfaces.
The
vent
for
this
appliance
shall
not
terminate:
a.
Near
soffit
vents
of
crawl
space
vents
or
other
areas
where
condensate
or
vapor
could
create
a
nuisance
or
hazard
or
property
damage;
or
b,
Where
condensate
vapor
could
cause
damage
or
could
be
detrimental
to
the
operation
of
regulators,
relief
valves,
or
other
equipment.
Fig.
45
-
Direct
Vent
Termination
Clearance
56
Avoid
venting
under
a
deck
or
large
overhang.
Recirculation
could
occur
and
cause
performance
or
system
problems.
Ice
build-up
may
occur.

Other manuals for Carrier 59SC2A

Related product manuals