EasyManua.ls Logo

Carrier 59SC2A - Operation and Maintenance Procedures; Start-Up, Adjustment, and Safety Check

Carrier 59SC2A
84 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
59SC2A
START-UP,
ADJUSTMENT,
AND
SAFETY
CHECK
General
1.
Furnace
must
have
a
115-v
power
supply
properly
connec-
ted
and
grounded.
NOTE:
Proper
polarity
must
be
maintained
for
115-v
wiring.
Control
status
indicator
light
flashes
rapidly and
furnace
does
not
operate
if
polarity
is
incorrect
or
if
the
furnace
is
not
grounded.
2.
Thermostat
wire
connections
at
terminals
R,
W,
G,
Y1
and
Y/Y2
must
be
made
at
24-v
terminal
block
on
furnace
con-
trol.
3.
Natural
gas
service
pressure
must
not
exceed
0.5
psig (14-
in.
w.c.,
350
Pa),
but
must
be
no
less
than
0.16
psig
(4.5-in.
w.c.,
1125
Pa).
4.
Blower
door
must
be
in
place
to
complete
115-v
electrical
circuit
and
supply
power
to
the
furnace
components.
4&
CAUTION
UNIT
OPERATION
HAZARD
Failure
to
follow
this
caution
may
result
in
intermittent
unit
operation
or
performance
satisfaction.
These
furnaces
are
equipped
with
a
manual
reset
limit
switch
in
burner
assembly.
This
switch
opens
and
shuts
off
power
to
the
gas
valve
if
an
overheat
condition
(flame
rollout)
occurs
in
the
burner
assembly/enclosure.
Correct
inadequate
combustion-air
supply,
improper
gas
pressure
setting,
improper
burner
or
gas
orifice
positioning,
or
improper
venting
condition
before
resetting
switch.
DO
NOT
jumper
this
switch.
Before
operating
furnace,
check
flame
rollout
manual
reset
switch
for
continuity.
If
necessary,
press
button
to
reset
switch.
EAC-1
(115vac)
terminal
is
energized
whenever
blower
operates.
HUM
(24vac)
terminal
is
only
energized
when
the
draft
inducer
is
energized
in
heating.
Prime
Condensate
Trap
with
Water
CARBON
MONOXIDE
POISONING
HAZARD
Failure
to
follow
these
warnings
could
result
in
personal
injury
or
death.
Failure
to
use
a
properly
configured
trap
or
NOT
water-priming
trap
before
operating
furnace
may
allow
positive
pressure
vent
gases
to
enter
the
structure
through
drain
tube.
Vent
gases
contain
carbon
monoxide
which
is
tasteless
and
odorless.
4&
CAUTION
UNIT
OPERATION
HAZARD
Failure
to
follow
this
caution
may
result
in
intermittent
unit
operation
or
performance
satisfaction.
Condensate
trap
must
be
PRIMED
or
proper
draining
may
not
occur.
The
condensate
trap
has
two
internal
chambers
which
can
ONLY
be
primed
by
pouring
water
into
the
inducer
drain
side
of
condensate
trap.
1.
Remove
upper
and
middie
collector
box
drain
plugs
oppos-
ite
of
the
condensate
trap.
See
Fig.
59.
.
Connect
field-supplied
5/8-in.
(16
mm)
ID
tube
with
at-
tached
funnel
to
upper
collector
box
drain
connection.
See
Fig. 59).
3.
Pour
one
quart
(liter)
of
water
into
funnel/tube.
Water
should
run
through
collector
box,
overfill
condensate
trap,
and
flow
into
open
field
drain.
bo
4.
Remove
funnel;
replace
collector
box
drain
plug.
5.
Connect
field-supplied
5/8-in.
(16
mm)
ID
tube
to
middle
collector
box
drain
port.
6.
Pour
one
quart
(liter)
of
water
into
funnel/tube.
Water
should
run
through
collector
box,
overfill
condensate
trap,
and
flow
into
open
field
drain.
7.
Remove
funnel
and
tube
from
collector
box
and
replace
col-
lector
box
drain
plug.
Purge
Gas
Lines
If
not
previously
done,
purge
the
lines
after
ail
connections
have
been
made
and
check
for
leaks.
CA
AUN
Le
FIRE
OR
EXPLOSION
HAZARD
Failure
to
follow
this
warning
could
result
in
personal
injury,
death,
and/or
property
damage.
Never
purge
a
gas
line
into
a
combustion
chamber.
Never
test
for
gas
leaks
with
an
open
flame.
Use
a
commercially
available
soap
solution
made
specifically
for
the
detection
of
leaks
to
check
all
connections.
A
fire
or
explosion
may
result
causing
property
damage,
personal
injury
or
loss
of
life.
Adjustments
A
A
Se
FIRE
HAZARD
Failure
to
follow
this
warning
could
result
in
personal
injury,
death
and/or
property
damage.
DO
NOT
bottom
out
gas
valve
regulator
adjusting
screw.
This
can
result
in
unregulated
manifold
pressure
and
result
in
excess
overfire
and
heat
exchanger
failures.
TION
FURNACE
DAMAGE
HAZARD
Failure
to
follow
this
caution
may
result
in
reduced
furnace
life.
DO
NOT
=
redrill
orifices.
Improper
drilling
(burrs,
out-of-round
holes,
etc.)
can
cause
excessive
burner
noise
and
misdirection
of
burner
flames.
This
can
result
in
flame
impingement
of
heat
exchangers,
causing
failures.
See
Fig.
54.
For
proper
operation
and
long term
reliability,
the
Furnace
input
rate
must
be
within
+/-2
percent
of
input
rate
on
furnace
rating
plate,
or
as
adjusted
for
altitude.
The
gas
input
rate
on rating
plate
is
for
installations
at
altitudes
up
to
2000
ft.
(609.6M).

Other manuals for Carrier 59SC2A

Related product manuals