86
CO2 Status R co2_stat AV 214
The current Zone Carbon Dioxide reading (CO
2
) from the Zs
sensor.
Comp #1 CS Status R cc1_cs_stat BV 224 Compressor #1 Current Sensor Status.
Comp #2 CS Status R cc2_cs_stat BV 227 Compressor #2 Current Sensor Status.
Compressor Disable SP R/W comp_dis_sp AV 541
The setpoint for Outside Air Temperature Compressor Disable
(Default is 32°F).
Compressor Disabled by
OAT
R comp_dis_oat BV 540
The current Compressor Disabled Status.
Condensate Overflow
Switch
R cos_stat BV 233
Condensate Overflow Switch Status (N.C.).
Cooling #1 Enable R clg1_en BV 551 The current Cooling #1 Enable Status.
Cooling #2 Enable R clg2_en BV 552 The current Cooling #2 Enable Status.
COS ALARM R cos_alarm BV 894 The current Condensate Overflow Switch Alarm Status.
CWV Action R/W cwv_action BV 640 Read/write to set type of Chilled Water Valve (Default is N.O.)
CWV Percentage R cwv_pct AV 288
The current Chilled Water Valve Modulation Status (UO-7
Percentage).
Dehumid. #1 Enable R dh1_en BV 565 The current Dehumidification #1 Enable Status.
Dehumid. #2 Enable R dh2_en BV 566 The current Dehumidification #2 Enable Status.
DH Mod. SP R/W dh_mod_sp AV 346 The setpoint for Dehumidification Modulation (53°F or 53%)
DH Mode Low Limit R/W dh_llim AV 344
The setpoint for Occupied Low Limit Dehumidification
Temperature (Default is 60°F).
DH SAT SP Occ R/W dh_sat_sp_o AV 341
The setpoint for Occupied Dehumidification Supply Air
Temperature (Default is 70°F).
DH SAT SP Unocc R/W dh_sat_sp_u AV 342
The setpoint for Unoccupied Dehumidification Supply Air
Temperature (Default is 75°).
DH SP Occ R/W dh_sp_o AV 337 The setpoint for Occupied Dehumidification #1 (Default is 55).
DH SP Unocc R/W dh_sp_u AV 338 The setpoint for Unoccupied Dehumidification #1 (Default is 65).
DH1 Sensor Status R dh1_stat AV 345 The current Dehumidification Sensor #1 Status
DH2 Sensor Status R dh2_sens_stat AV 349 The current Dehumidification Sensor #2 Status
DIG1 Minimum Output R/W dig1_min AV 647
Read/write Digital Compressor #1 Minimum Output (Default is
20%)
Digital Compressor #1
Percent
R dig_c1_pct AV 6401
The current Compressor #1 Modulation Status (UO-7
Percentage).
Digital Compressor #2
Percent
R dig_c2_pct AV 6501
The current Compressor #2 Modulation Status (UO-8
Percentage).
DR1 Status R dr1_stat BV 256 Defrost Relay #1 Status
DR2 Status R dr2_stat BV 257 Defrost Relay #2 Status
DX LAT #2 Status R dx_lat2_stat AV 245 The current Leaving Air Temperature for Dx coil #2 (DXLAT2).
DX LAT Status R dx_lat_stat AV 243 The current Leaving Air Temperature for Dx coil #1 (DXLAT).
DXLAT FAIL R dx_lat_failure BV 843 The current DXLAT Sensor Alarm Status.
DXLAT2 FAIL R dx_lat2_failure BV 844 The current DxLAT2 Sensor Alarm status.
ECAT FAIL R ecat_failure BV 831 The current ECAT Sensor Alarm status.
ECAT Status R ecat_stat AV 219 The current Entering Coil Air Temperature (ECAT).
ECON NOT R econ_not_fdd BV 962 The current FDD Alarm is Economizing when it should not.
Econ. MAT SP R/W econ_mat_sp AV 600
The setpoint for Economizer Mixed Air Temperature (Default is
65°F).
Econ. OAE SP R/W econ_oae_sp AV 549
The setpoint for Economizer Outside Air Enthalpy (default is
22btu/lb).
Econ. OAT Upper SP R/W econ_oat_usp AV 550
The setpoint for Economizer Outside Air Temperature (Default is
59°F).
ECRH FAIL R ecrh_failure BV 832 The current ECAT Sensor Alarm status.
ECRH Status R ecrh_stat AV 221 Entering Coil Relative Humidity Sensor Status (ECRH).
ECW ALARM R ecw_alarm BV 952 The current Energy Conservation Wheel Alarm Status.
ECW Command R ecw_cmd BV 247 Energy Conservation Wheel Start Command (BO-7)
ECW CS Status R ecw_cs_stat BV 222 Energy Conservation Wheel Current Sensor Status.
ECW Defrost ON R ecw_def_on BV 514 The current Energy Conservation Wheel Defrost Status
ECW Enable R ecw_en BV 513
The current Energy Conservation Wheel Enable Status (Default
is 25°F).
ECW HAND R ecw_hand_alarm BV 953 The current Energy Conservation Wheel Hand Alarm Status.
ECW VFD Frequency R ecwvfd_freq AV 284
The current Energy Conservation Wheel VFD Status (UO-5
Frequency)
EF ALARM R ef_alarm BV 860 The current Exhaust Fan Alarm Status.
EF AMS SP R/W ef_ams_sp AV 305
The setpoint for Exhaust Fan Air Monitoring Station (Default is
2000cfm)
EF DPT SP R/W ef_dpt_sp AV 302
The setpoint for Exhaust Fan Duct Pressure Transducer (Default
is 1 in. of H
2
O)
EF HAND R ef_hand_alarm BV 861 The current Exhaust Fan Hand Alarm Status.
EF Modulation R efmod_pct AV 287
The current Exhaust Fan Modulation Status
(UO-2 Percentage).
EF OA AMS Status R ef_oa_ams_stat AV 259
The current exhaust Fan, Supply Fan, or
Outdoor Air Monitoring Station Status (UI- 11).
EF PID Output Override R/W ef_pid_ovrd AV 639 Read/write Exhaust Fan PID Output for CAV (Percentage).
Table C — Mapping Points - Carrier 62X Rev. H - 100% Outdoor Air Air-to-Air (cont)
Display Name Read/Write
BACnet
Description
Reference Name Type ID