EF PID Output Override
Lock
R/W ef_pid_ovrd_lock BV 631
Read/write Exhaust Fan PID Output in Constant Air Volume
(CAV) Status.
EF-APS or CS Status R ef_aps_stat BV 221 Exhaust Fan Air Proving Switch or Current Sensor Status.
EM SHTDN R em_shtdn_alarm BV 895 The current Emergency Shutdown Alarm Status.
Em. Htg. Enable R ehtg_en BV 579 The current Emergency Heating Enable Status.
Emerg. Shutdown Enable R/W emsd_en BV 821 The current Emergency Shutdown Enable Status.
Emergency Shutdown
Status
R emsd_status BV 822
The current Emergency Shutdown Status.
EMR/EMSD Status R emrsd_stat BV 234 Emergency Relay/ Emergency Shutdown Switch Status (N.C.).
Enable BAS Mon OAT/
OARH
R/W en_bas_mon_oa BV 1100
Read/write point will Enables BAS Monitoring of OAT/OARH
Sensors.
Enable BAS Monitor
Schedule
R/W en_bas_mon BV 106
BAS communication lost code. Enables the code to allow the
BAS control to change to the local schedule in the controller.
Enable FDD Alarms R/W fdd_alarm_en BV 960 Read/write point to Enable FDD Alarms.
Entering Coil Air Dew
Point
R eca_dewpoint AV 262
The current Entering Coil Air Dew Point Status
Entering coil Air
Enthalpy
R ec_enthalpy AV 263
The current Entering Coil Air Enthalpy Status
EXCESS OA R excess_oa_fdd BV 964 The current FDD Alarm is allow to much OA.
Field BAS Comm. Status R/W bas_comm_status BV 110
BAS communication lost code. Read/write point must change
state before BAS lost delay timer expires.
FP1 ALARM R fp1_alarm BV 871 The current Freeze Protection #1 Alarm Status.
FP1 STOP R fp1_stop_alarm BV 872 The current Freeze Protection #1 Stop Alarm Status.
FP2 ALARM R fp2_alarm BV 885 The current Freeze Protection #2 Alarm Status.
FP2 STOP R fp2_stop_alarm BV 886 The current Freeze Protection #2 Stop Alarm Status.
Freeze Protection LSP R/W fp_lsp AV 323
The setpoint for Lower Compressor Freeze Lockout Protection
(Default is 38°F).
Freeze Protection MSP R/W fp_msp AV 322
The setpoint for Middle Compressor Freeze Lockout Protection
(Default is 45°F).
Freeze Protection USP R/W fp_usp AV 321
The setpoint for Upper Compressor Freeze Lockout Protection
(Default is 55°F).
FRZ Status R frz_stat BV 231 Freezestat Status in WSHP (N.C.).
FZT ALARM R fzt_alarm BV 830 The current Water Freezestat Alarm status.
Heat Mod. Minimum
Output
R/W htg_mod_min AV 677
Read/write Heating Minimum Output (Default is 0%)
Heat Modulation R htg_mod AV 286 The current Heat Modulation Status (UO-6 Percentage)
Heat PID Output Override R/W htg_pid_ovrd AV 678 Read/write Heating PID Output for CAV (Percentage).
Heat PID Output Override
Lock
R/W htg_pid_ovrd_lock BV 671
Read/write Heating PID Output in Constant Air Volume (CAV)
Status.
Heat Pump #1 Enable R hp1_en BV 571 The current Heat Pump #1 Enable Status.
Heat Pump #2 Enable R hp2_en BV 572 The current Heat Pump #2 Enable Status
Heating Supports Reheat R/W htg_rh_en BV 563 Read/write point Enables heating to support HGRH.
HGRH Mod. Minimum
Output
R/W hgrh_mod_min AV 668
Read/write HGRH Minimum Output (Default is 0%)
HGRH Modulation R hgrh_mod AV 285
The current Hot Gas Reheat Modulation Status (UO-4
Percentage)
HGRH PID Output
Override
R/W hgrh_pid_ovrd AV 669
Read/write HGRH PID Output for CAV (Percentage).
HGRH PID Output
Override Lock
R/W
hgrh_pid_ovrd_loc
k
BV 661
Read/write HGRH PID Output in Constant Air Volume (CAV)
Status.
HIGH CO2 R high_co2_alarm BV 826 The current High CO2 Alarm status.
High Supply DPT SP R/W high_sfdpt_sp AV 804
The setpoint for High Supply Fan Duct Pressure Transducer
Alarm (Default is 5 in. of H2O).
HPS #1 Status R hps1_stat BV 226 High Pressure Switch #1 Status.
HPS #2 Status R hps2_stat BV 229 High Pressure Switch #2 Status.
HPS1 ALARM R hps1_alarm BV 867 The current High Pressure Switch #1 Alarm Status.
HPS1 STOP R hps1_stop_alarm BV 868 The current High Pressure Switch #1 Stop Alarm.
HPS2 ALARM R hps2_alarm BV 881 The current High Pressure Switch #2 Alarm Status.
HPS2 STOP R hps2_stop_alarm BV 882 The current High Pressure Switch #2 Stop Alarm.
HSAT ALARM R hsat_alarm BV 892 The current High Supply Air Temperature Alarm Status.
HSDP ALARM R hsdp_alarm BV 858 The current High Supply Duct Pressure Alarm Status.
HSDP STOP R hsdp_stop_alarm BV 859 The current High Supply Duct Pressure Stop Alarm Status.
HT FAIL R heat_failure BV 891 The current Heat Failure Alarm Status.
Htg Enable SP R/W htg_en_sp AV 351 The setpoint for Heating #1 Enable. (Default is 55°F).
Htg Mode High Limit
Setpoint
R/W htg_hlim AV 360
The setpoint for Occupied High Limit Dehumidification
Temperature (Default is 60°F).
Htg SAT SP Occ R/W htg_sat_sp_o AV 354
The setpoint for Occupied Heating Supply Air Temperature
(Default is 70°F or 90°F Recirc).
Htg SAT SP Unocc R/W htg_sat_sp_u AV 355
The setpoint for Unoccupied Heating Supply Air Temperature
(Default is 90°F).
IN0/11_ZN/EFdpt Status R zn_ef_dpt11_stat AV 253
The current Zone or Exhaust Fan Duct Pressure Transducer
Status (UI-11)
Table C — Mapping Points - Carrier 62X Rev. H - 100% Outdoor Air Air-to-Air (cont)
Display Name Read/Write
BACnet
Description
Reference Name Type ID