145
Table 38 — Air Handler VFD Factory-Set Parameters (cont)
* Factory Programmed as follows: For 208-230v / 60 Hz = 208, 460v / 60 Hz = 460, 200-230v / 50 Hz = 200, 380 / 50 Hz = 400.
† Motor Nameplate Amps. Factory programmed per Programmed Settings in Table 37. This value should always be compared to the actual motor nameplate value
before start-up.
**Maximum Output Amps — Factory programmed per Table 37.
GROUP
NUMBER
PARAMETER
NUMBER
DESCRIPTION
VFD DRIVE ONLY
PARAMETERS
VFD WITH E-CLIPSE DESCRIPTION /
PARAMETER
31
3101 Number of Retries 2 2
3102 Trial Time 600 sec. 600 sec.
3103 Delay Time 5 sec. 5 sec.
3104 AR Overcurrent Enable Enable
3105 AR Overvoltage Enable Enable
3106 AR Under voltage Enable Enable
3107 AR AI< Minimum (0) Disable (0) Disable
3108 AR External Fault (0) Disable (0) Disable
34
3415 Signal Parameter 3 Speed Speed
3416 Signal 3 Minimum 0 0
3417 Signal 3 Maximum 30000 30000
3418 Output 3 DSP From 0 0
3419 Output 3 DSP units rpm rpm
3420 Output 3 Minimum 0 0
3421 Outpu
t 3 Maximum 3000 3000
40
4001 Gain 0.7 0.7
4002 Integration Time 30 sec. 30 sec.
4005 Error Value Invert no no
4006 Units volts volts
4007 Display Format x.xxx x.xxx
4010 Setpoint Select Internal Internal
4011 Internal Setpoint Field Program (0.0v~10,0v) Field Program (0.0v~10,0v)
4012 Setpoint Minimum 0 v 0 v
4013 Setpoint Maximum 10.0v 10.0v
4016 ACT 1 Input AI-2 AI-2
4027 PID Parameter Set SET 1 SET 1
53
5301 EFB Protocol ID 0 118
5303 EFB Baud Ra
te 9.6 76.8
5304 EFB Parity 8 NONE 1 8 EVEN 1
5305 EFB Control Profile ABB DRV LIM DCU PROFILE
5310 EFB PAR 10 0 103
5311 EFM PAR 11 0 104
98 9802 Comm Prot SEL NOT SEL STD MODBUS