25
Table 8B — 19XR Waterbox Cover Weights — SI (kg)
LEGEND NOTE: Weight for NIH 2-pass cover, 1034 kPa, is included in the
heat exchanger weights shown in Tables 6A and 6B.
WATERBOX DESCRIPTION
COOLER
FRAME 1 FRAME 2 FRAME 3
STANDARD
NOZZLES
FLANGED
STANDARD
NOZZLES
FLANGED
STANDARD
NOZZLES
FLANGED
NIH, 1 Pass Cover, 1034 kPa 80 92 130 144 130 144
NIH, 2 Pass Cover, 1034 kPa 84 99 130 154 130 154
NIH, 3 Pass Cover, 1034 kPa 82 88 133 141 133 141
MWB End Cover, 1034 kPa — — 143 143 143 143
NIH/MWB Return Cover, 1034 kPa 62 62 110 110 110 110
NIH, 1 Pass Cover, 2068 kPa 112 137 186 220 186 220
NIH, 2 Pass Cover, 2068 kPa 116 147 186 235 186 235
NIH, 3 Pass Cover, 2068 kPa 115 131 196 212 196 212
NIH Plain End Cover, 2068 kPa 79 79 132 132 132 132
MWB End Cover, 2068 kPa — — 281 281 281 281
MWB Return Cover, 2068 kPa — — 202 202 202 202
WATERBOX
DESCRIPTION
CONDENSER
FRAME 1 FRAME 2 FRAME 3
STANDARD
NOZZLES
FLANGED
STANDARD
NOZZLES
FLANGED
STANDARD
NOZZLES
FLANGED
NIH, 1 Pass Cover, 1034 kPa 80 92 118 135 118 135
NIH, 2 Pass Cover, 1034 kPa 84 99 120 144 120 144
NIH, 3 Pass Cover, 1034 kPa 82 88 123 131 123 131
MWB End Cover, 1034 kPa — — 106 106 106 106
NIH/MWB Return Cover, 1034 kPa 62 62 102 102 102 102
NIH, 1 Pass Cover, 2068 kPa 112 137 172 206 172 206
NIH, 2 Pass Cover, 2068 kPa 116 147 172 220 172 220
NIH, 3 Pass Cover, 2068 kPa 115 131 182 198 182 198
NIH Plain End Cover, 2068 kPa 79 79 122 122 122 122
MWB End Cover, 2068 kPa — — 215 215 215 215
MWB Return Cover, 2068 kPa — — 163 163 163 163
NIH — Nozzle-in-Head
MWB — Marine Waterbox