31
Step 3 — Install Machine Supports
INSTALL STANDARD ISOLATION — Figures 11 and 12
show the position of support plates and shear flex pads, which
together form the standard machine support system.
INSTALL ACCESSORY ISOLATION (IF
REQUIRED) — Uneven floors or other considerations may
dictate the use of accessory soleplates (supplied by Carrier
for field installation) and leveling pads. Refer to Fig. 11 and 13.
Level machine by using jacking screws in isolation sole-
plates. Use a level at least 24-in. (600 mm) long.
For adequate and long lasting machine support, proper
grout selection and placement is essential. Carrier recommends
that only pre-mixed, epoxy type, non-shrinking grout be used
for machine installation. Follow manufacturer’s instructions in
applying grout.
1. Check machine location prints for required grout
thickness.
2. Carefully wax jacking screws for easy removal from
grout.
3. Grout must extend above the base of the soleplate and
there must be no voids in grout beneath the plates.
4. Allow grout to set and harden, per manufacturer’s in-
structions, before starting machine.
5. Remove jacking screws from leveling pads after grout
has hardened.
IMPORTANT: Chiller housekeeping pad, anchor bolts, and
attachment points that are designed by others must be in
accordance with all applicable national and local codes.
19XR,XRV
HEAT EXCHANGER
SIZE
DIMENSIONS
ABCDEFG
FT-IN. MM FT-IN. MM FT-IN. MM FT-IN. MM FT-IN. MM
FT-
IN.
MM
FT-
IN.
MM
10-12
10- 7
1
/
4
3232 4-10
1
/
4
1480 0-1 25 0-3
5
/
8
92 1-3
1
/
4
382 0-9 229 0-
1
/
2
13
15-17
12-10
3
/
4
3931 4-10
1
/
4
1480 0-1 25 0-3
5
/
8
92 1-3
1
/
4
382 0-9 229 0-
1
/
2
13
20-22
10- 7
1
/
4
3232 5- 4
1
/
4
1632 0-1 25 0-3
5
/
8
92 1-3
1
/
4
382 0-9 229 0-
1
/
2
13
30-32
12-10
3
/
4
3931 5- 4
1
/
4
1632 0 0 0-3
5
/
8
92 1-3
1
/
4
382 0-9 229 0-
1
/
2
13
35-37
14- 7
1
/
4
4451 5- 4
1
/
4
1632 0 0 0-3
5
/
8
92 1-3
1
/
4
382 0-9 229 0-
1
/
2
13
40-42
12-10
3
/
4
3931 6- 0 1829 0-1
1
/
2
38 0-3
5
/
8
92 1-3
1
/
4
382 0-9 229 0-
1
/
2
13
45-47
14- 7
1
/
4
4451 6- 0 1829 0-1
1
/
2
38 0-3
5
/
8
92 1-3
1
/
4
382 0-9 229 0-
1
/
2
13
50-54, 5A-5C, 5K-5R
12-10
3
/
4
3931 6- 5
1
/
2
1968 0-
1
/
2
13 0-3
5
/
8
92 1-3
1
/
4
382 0-9 229 0-
1
/
2
13
55-59, 5F-5H, 5T-5Z
14- 7
1
/
4
4451 6- 5
1
/
2
1968 0-
1
/
2
13 0-3
5
/
8
92 1-3
1
/
4
382 0-9 229 0-
1
/
2
13
60-64, 6K-6R
12-10
3
/
4
3931 6- 9
1
/
2
2070 0-
1
/
2
13 0-3
5
/
8
92 1-3
1
/
4
382 0-9 229 0-
1
/
2
13
65-69, 6T-6Z
14- 7
1
/
4
4451 6- 9
1
/
2
2070 0-
1
/
2
13 0-3
5
/
8
92 1-3
1
/
4
382 0-9 229 0-
1
/
2
13
70-74, 7K-7R
15- 1
7
/
8
4620 7-10
1
/
2
2400 0-
1
/
4
60-6
15
/
16
176 1-10 559 1-4 406 0-
3
/
4
19
75-79, 7T-7Z
17- 1
7
/
8
5229 7-10
1
/
2
2400 0-
1
/
4
60-6
15
/
16
176 1-10 559 1-4 406 0-
3
/
4
19
80-84, 8K-8R
15- 1
7
/
8
4620 8- 9
3
/
4
2686 0-
15
/
16
24 0-6
15
/
16
176 1-10 559 1-4 406 0-
1
/
16
2
85-89, 8T-8Z
17- 1
7
/
8
5229 8- 9
3
/
4
2686 0-
15
/
16
24 0-6
15
/
16
176 1-10 559 1-4 406 0-
1
/
16
2
Fig. 11 — 19XR,XRV Machine Footprint