CL-9
19XR, XRV PIC II SETUP2 TABLE CONFIGURATION SHEET
DESCRIPTION STATUS UNITS DEFAULT VALUE
Capacity Control
Proportional Inc Band 2 to 10 6.5
Proportional DEC Band 2 to 10 6.0
Proportional ECW Gain 1 to 3 2.0
Guide Vane Travel Limit 30 to 100 % 80
VFD Speed Control
VFD Option 0/1 DSABLE/ENABLE DSABLE
VFD Gain 0.1 to 1.5 0.75
VFD Increase Step 1 to 5 % 2
VFD Minimum Speed 65 to 100 % 70
VFD Maximum Speed 90 to 100 % 100
VFD Start Speed 65 to 100 % 100
VFD Surge Line Gain 2.0 to 3.5 2.0
VFD Current Limit 0 to 99999 amps 250