APPENDIX A — PIC 5 SCREEN AND TABLE STRUCTURE (cont)
Hydraulic Status
LEGEND
*Default value is shown only if configurable in this table.
CCN TABLE NAME: HYDRLIC
PIC 5 PATH: Main Menu Hydraulic Status
LINE PIC 5 DESCRIPTION CCN NAME RANGE
DEFAULT
VALUE*
UNIT READ/WRITE
1 Chilled Water Pump CHWP OFF/ON RO
2 Condenser Water Flow CDW_FLOW NO/YES RO
3 Cond Water Flow Value CDW_FV 0-10,000 0.0 GPM RO
4 Entering Cond Water Pres COND_EWP –6.7 to 420.0 psig RO
5 Leaving Cond Water Pres COND_LWP –6.7 to 420.0 psig RO
6 Condenser Water Delta P cdw_off –10.0-10.0 0.0 psi RW
7 Condenser Delta P Offset cdw_off –10.0-10.0 0.0 psig RW
8 Cond Water Pulldown/Min cdw_pull –20 to 20.0 °F RO
9 Condenser Water Pump CDWP OFF/ON RO
10 Chilled Water Pump
11 Chilled Water Flow CHW_FLOW NO/YES RO
12 Chilled Water Flow Value CHW_FV –10.0 to 10.0 0.0 psi RW
13 Entering Chilled Water P EVAP_EWP –6.7 to 420.0 psig RO
14 Leaving Chilled Water P EVAP_LWP –6.7 to 420.0 psig RO
15 Chilled Water Delta P chw_pd –6.7 to 420.0 psig RO
16 Chilled Delta P Offset chw_off –10 to 10.00 0.0 psig RW
17 Chilled Water Pulldown/Min chw_pull –20 to 20.0 °F RO
18 Chilled Water Flow Input CHWF_IN 4 to 20 mA RO
19 Cond Water Flow Input CDWF_IN 4 to 20 mA RO
20 Chilled Water Pres Drop CHW_PDMA 4 to 20 mA RO
21 Cond Water Pres Drop CDW_PDMA 4 to 20 mA RO
22 Evap Water Flow Switch EVAP_FS OPEN/CLOSE
23 Cond Water Flow Switch COND_FS OPEN/CLOSE
24 Tower Fan Relay High TFR_HI OFF/ON RO
25 Tower Fan Relay Low TFR_LO OFF/ON RO
26 Controlled Water DT ctrlw_dt –40.0 to 245.0 °F RO
27 Cond Water Flow Status
0=Fail or Not Started
1=Success, 2=Verifying
cdw_fl_s 0 to 2 RO
28 Chilled Water Flow Status
0=Fail or Not Started
1=Success, 2=Verifying
chw_fl_s 0 to 2 RO
29 Pumpdown/Lockout State pdown_st 0 to 255 RO
RO — Read Only
RW — Read/Write