APPENDIX A — PIC 5 SCREEN AND TABLE STRUCTURE (cont)
Evap Pressure Sensor
Cond Pressure Sensor
Eco Pressure Sensor
Diff Pressure Sensor
LEGEND *Default value is shown only if configurable in this table.
CCN TABLE NAME: PRSCAL01
PIC 5 PATH: Main Menu Maintenance Menu Pressure Sensor Calib Evap Pressure Sensor
LINE PIC 5 DESCRIPTION CCN NAME RANGE
DEFAULT
VALUE*
UNIT READ/WRITE
1 Evap Pressure Sensor
2 Calibration Enable cal_en DSABLE/ENABLE DSABLE RW
3 Current Pressure cur_pres psig RO
4 Calib Press1 (0 PSI) cal_p1 9 digit numeric string 0 psig RW
5 Calib Press2 (100-250PSI) cal_p2 9 digit numeric string 0 psig RW
6 Calibrated Slope cal_s RO
7 Calibrated Intercept cal_i RO
8 Calibration Completed cal_st NO/YES NO RO
CCN TABLE NAME: PRSCAL02
PIC 5 PATH: Main Menu Maintenance Menu Pressure Sensor Calib Cond Pressure Sensor
LINE PIC 5 DESCRIPTION CCN NAME RANGE
DEFAULT
VALUE*
UNIT READ/WRITE
1 Cond Pressure Sensor
2 Calibration Enable cal_en DSABLE/ENABLE DSABLE RW
3 Current Pressure cur_pres psig RO
4 Calib Press1 (0 PSI) cal_p1 9 digit numeric string 0 psig RW
5 Calib Press2 (100-250PSI) cal_p2 9 digit numeric string 0 psig RW
6 Calibrated Slope cal_s RO
7 Calibrated Intercept cal_i RO
8 Calibration Completed cal_st NO/YES NO RO
CCN TABLE NAME: PRSCAL03
PIC 5 PATH: Main Menu Maintenance Menu Pressure Sensor Calib Eco Pressure Sensor
LINE PIC 5 DESCRIPTION CCN NAME RANGE
DEFAULT
VALUE*
UNIT READ/WRITE
1 Eco Pressure Sensor
2 Calibration Enable cal_en DSABLE/ENABLE DSABLE RW
3 Current Pressure cur_pres psig RO
4 Calib Press1 (0 PSI) cal_p1 9 digit numeric string 0 psig RW
5 Calib Press2 (100-250PSI) cal_p2 9 digit numeric string 0 psig RW
6 Calibrated Slope cal_s RO
7 Calibrated Intercept cal_i RO
8 Calibration Completed cal_st NO/YES NO RO
CCN TABLE NAME: PRSCAL04
PIC 5 PATH: Main Menu Maintenance Menu Pressure Sensor Calib Diff Pressure Sensor
LINE PIC 5 DESCRIPTION CCN NAME RANGE
DEFAULT
VALUE*
UNIT READ/WRITE
1 Diff Pressure Sensor
2 Calibration Enable cal_en DSABLE/ENABLE DSABLE RW
3 Current Pressure cur_pres psig RO
4 Calib Press1 (0 PSI) cal_p1 9 digit numeric string 0 psig RW
5 Calib Press2 (100-250PSI) cal_p2 9 digit numeric string 0 psig RW
6 Calibrated Slope cal_s RO
7 Calibrated Intercept cal_i RO
8 Calibration Completed cal_st NO/YES NO RO