APPENDIX A — PIC 5 SCREEN AND TABLE STRUCTURE (cont)
Oil Sump Pressure
Oil Supply Pressure
Evap Entering Water P
Evap Leaving Water P
LEGEND *Default value is shown only if configurable in this table.
CCN TABLE NAME: PRSCAL05
PIC 5 PATH: Main Menu Maintenance Menu Pressure Sensor Calib Oil Sump Pressure
LINE PIC 5 DESCRIPTION CCN NAME RANGE
DEFAULT
VALUE*
UNIT READ/WRITE
1 Oil Sump Pressure
2 Calibration Enable cal_en DSABLE/ENABLE DSABLE RW
3 Current Pressure cur_pres psig RO
4 Calib Press1 (0 PSI) cal_p1 9 digit numeric string 0 psig RW
5 Calib Press2 (100-250PSI) cal_p2 9 digit numeric string 0 psig RW
6 Calibrated Slope cal_s 0 RO
7 Calibrated Intercept cal_i 0 RO
8 Calibration Completed cal_st NO/YES 0 RO
CCN TABLE NAME: PRSCAL06
PIC 5 PATH: Main Menu Maintenance Menu Pressure Sensor Calib Oil Supply Pressure
LINE PIC 5 DESCRIPTION CCN NAME RANGE
DEFAULT
VALUE*
UNIT READ/WRITE
1 Oil Supply Pressure
2 Calibration Enable cal_en DSABLE/ENABLE DSABLE RW
3 Current Pressure cur_pres psig RO
4 Calib Press1 (0 PSI) cal_p1 9 digit numeric string 0 psig RW
5 Calib Press2 (100-250PSI) cal_p2 9 digit numeric string 0 psig RW
6 Calibrated Slope cal_s RO
7 Calibrated Intercept cal_i RO
8 Calibration Completed cal_st NO/YES NO RO
CCN TABLE NAME: PRSCAL07
PIC 5 PATH: Main Menu Maintenance Menu Pressure Sensor Calib Evap Entering Water P
LINE PIC 5 DESCRIPTION CCN NAME RANGE
DEFAULT
VALUE*
UNIT READ/WRITE
1 Evap Entering Water P
2 Calibration Enable cal_en DSABLE/ENABLE DSABLE RW
3 Current Pressure cur_pres psig RO
4 Calib Press1 (0 PSI) cal_p1 9 digit numeric string 0 psig RW
5 Calib Press2 (100-250PSI) cal_p2 9 digit numeric string 0 psig RW
6 Calibrated Slope cal_s RO
7 Calibrated Intercept cal_i RO
8 Calibration Completed cal_st NO/YES NO RO
CCN TABLE NAME: PRSCAL08
PIC 5 PATH: Main Menu Maintenance Menu Pressure Sensor Calib Evap Leaving Water P
LINE PIC 5 DESCRIPTION CCN NAME RANGE
DEFAULT
VALUE*
UNIT READ/WRITE
1 Evap Leaving Water P
2 Calibration Enable cal_en DSABLE/ENABLE DSABLE RW
3 Current Pressure cur_pres psig RO
4 Calib Press1 (0 PSI) cal_p1 9 digit numeric string 0 psig RW
5 Calib Press2 (100-250PSI) cal_p2 9 digit numeric string 0 psig RW
6 Calibrated Slope cal_s RO
7 Calibrated Intercept cal_i RO
8 Calibration Completed cal_st NO/YES NO RO
RO Read Only
RW Read/Write