89
APPENDIX A — PIC 5 SCREEN AND TABLE STRUCTURE (cont)
Cond Entering Water P
Cond Leaving Water P
LEGEND *Default value is shown only if configurable in this table.
Temp Sensor Calib
LEGEND *Default value is shown only if configurable in this table.
CCN TABLE NAME: PRSCAL09
PIC 5 PATH: Main Menu Maintenance Menu Pressure Sensor Calib Cond Entering Water P
LINE PIC 5 DESCRIPTION CCN NAME RANGE
DEFAULT
VALUE*
UNIT READ/WRITE
1 Cond Entering Water P
2 Calibration Enable cal_en DSABLE/ENABLE DSABLE RW
3 Current Pressure cur_pres psig RO
4 Calib Press1(0 PSI) cal_p1 9 digit numeric string 0 psig RW
5 Calib Press2 (100-250PSI) cal_p2 9 digit numeric string 0 psig RW
6 Calibrated Slope cal_s RO
7 Calibrated Intercept cal_i RO
8 Calibration Completed cal_st NO/YES NO RO
CCN TABLE NAME: PRSCAL10
PIC 5 PATH: Main Menu Maintenance Menu Pressure Sensor Calib Cond Leaving Water P
LINE PIC 5 DESCRIPTION CCN NAME RANGE
DEFAULT
VALUE*
UNIT READ/WRITE
1 Cond Leaving Water P
2 Calibration Enable cal_en DSABLE/ENABLE DSABLE RW
3 Current Pressure cur_pres psig RO
4 Calib Press1(0 PSI) cal_p1 9 digit numeric string 0 psig RW
5 Calib Press2 (100-250PSI) cal_p2 9 digit numeric string 0 psig RW
6 Calibrated Slope cal_s RO
7 Calibrated Intercept cal_i RO
8 Calibration Completed cal_st NO/YES NO RO
RO — Read Only
RW — Read/Write
CCN TABLE NAME: TEMP_CAL
PIC 5 PATH: Main Menu Maintenance Menu Temp Sensor Calib
LINE PIC 5 DESCRIPTION CCN NAME RANGE
DEFAULT
VALUE*
UNIT READ/WRITE
1 Entering Chilled Water ECW °F RO
2 ECW Sensor Raw Temp ECW_RAW °F RO
3 ECW Temperature Offset ECW_OFF –2.0 to 2.0 0 ^F RW
4 Leaving Chilled Water LCW °F RO
5 LCW Sensor Raw Temp LCW_RAW °F RO
6 LCW Temperature Offset LCW_OFF –2.0 to 2.0 0 ^F RW
7 Entering Condenser Water ECDW °F RO
8 ECDW Sensor Raw Temp ECDW_RAW °F RO
9 ECDW Temperature Offset ECDW_OFF –2.0 to 2.0 0 ^F RW
10 Leaving Condenser Water LCDW °F RO
11 LCDW Sensor Raw Temp LCDW_RAW °F RO
12 LCDW Temperature Offset LCDW_OFF –2.0 to 2.0 0 ^F RW
RO — Read Only
RW — Read/Write