APPENDIX A — PIC 5 SCREEN AND TABLE STRUCTURE (cont)
System Status
LEGEND *Default value is shown only if configurable in this table.
Alarms Menu Description
Alarm Reset
LEGEND *Default value is shown only if configurable in this table.
NOTE: For more information about viewing and resetting alarms,
see the Diagnostics and Troubleshooting section on page 32.
CCN TABLE NAME: SYS_STAT
PIC 5 PATH: Main Menu Maintenance Menu System Status
LINE PIC 5 DESCRIPTION CCN NAME RANGE
DEFAULT
VALUE*
UNIT READ/WRITE
1 System Control Mode sys_ctlm RO
2 System Status sys_stat RO
3 Master Run Status mas_stat RO
4 Slave Run Status sla_stat RO
5 System Percent Load sys_perl % RO
6 System KW sys_kw kW RO
7 System Control Point sys_stlp °F RO
8 System Demand Limit sys_dem % RO
9 Supply Liquid Temp sys_supt RO
10 Return Liquid Temp sys_rent RO
RO — Read Only
ICON DISPLAYED TEXT ACCESS ASSOCIATED TABLE
PAGE
NO.
Reset Alarms All ALARMRST 91
Current Alarms All CUR_ALM
History Alarms All ALMHIST1
Prognostics All HEALTH
CCN TABLE NAME: ALARMRST
PIC 5 PATH: Main Menu Alarm Menu Alarm Reset
LINE PIC 5 DESCRIPTION CCN NAME RANGE
DEFAULT
VALUE*
UNIT READ/WRITE
1 Alarm Reset RST_ALM NO/YES NO RW
2 Alarm State ALM_STAT RO
3 Current Alarm 1 alarm_1c RO
4 Current Alarm 2 alarm_2c RO
5 Current Alarm 3 alarm_3c RO
6 Current Alarm 4 alarm_4c RO
7 Current Alarm 5 alarm_5c RO
8 Jbus Current Alarm 1 alarm_1 RO
9 Jbus Current Alarm 2 alarm_2 RO
10 Jbus Current Alarm 3 alarm_3 RO
11 Jbus Current Alarm 4 alarm_4 RO
12 Jbus Current Alarm 5 alarm_5 RO
RO — Read Only
RW — Read/Write