21
4 - PHYSICAL AND ELECTRICAL DATA FOR 30XB UNITS
4.2 - Physical data 30XBP
30XBP-250 to 800
30XBP 250 300 350 400 450 500 600 700 750 800
Sound levels
Standard unit
Sound power
(1)
dB(A) 99 99 99 99 101 99 101 99 103 103
Sound pressure at 10 m
(2)
dB(A) 67 67 67 67 69 67 68 67 70 70
Unit + option 15
(3)
Sound power
(1)
dB(A) 93 93 94 95 95 95 97 96 97 98
Sound pressure at 10 m
(2)
dB(A) 61 61 62 63 63 63 65 63 64 65
Unit + option 15LS
(3)
Sound power
(1)
dB(A) 87 87 87 90 91 91 93 92 94 94
Sound pressure at 10 m
(2)
dB(A) 55 55 55 58 59 59 60 59 61 61
Unit + option 15LS+
(3)
Sound power
(1)
dB(A) - - - - - - - - - -
Sound pressure at 10 m
(2)
dB(A) - - - - - - - - - -
Dimensions
Standard unit
Length mm 3604 3604 3604 4798 4798 5992 7186 7186 7186 7186
Width mm 2253 2253 2253 2253 2253 2253 2253 2253 2253 2253
Height mm 2297 2297 2297 2297 2297 2297 2297 2297 2297 2297
Operating weight
(4)
Standard unit kg 3190 3224 3245 3834 3899 4261 4962 5093 5376 5687
Unit + option 15
(3)
kg 3458 3492 3513 4133 4198 4560 5293 5424 5707 6018
Compressors 06T semi-hermetic screw compressor, 50 r/s
Circuit A 1 1 1 1 1 1 1 1 1 1
Circuit B 1 1 1 1 1 1 1 1 1 1
No. of control stages
Refrigerant for standard unit
(4)
R134a
Circuit A kg 37 35 35 51 52 54 58 58 65 69
teqCO
2
52,9 50,1 50,1 72,2 74,4 76,5 82,9 82,9 93,0 98,7
Circuit B kg 38,5 36 37 36,5 37 32,5 59 62 58 65
teqCO
2
55,1 51,5 52,9 52,2 52,9 46,5 84,4 88,7 82,9 93,0
Oil
Circuit A l 20,8 20,8 20,8 23,5 23,5 23,5 23,5 23,5 27,6 27,6
Circuit B l 20,8 20,8 20,8 20,8 20,8 20,8 23,5 23,5 23,5 23,5
(1) In dB ref=10-12 W, ‘A’ weighted. Declared dual-number noise emission values in accordance with ISO 4871 with an associated uncertainty of +/-3dB(A). Measured in
accordance with ISO 9614-1 and certied by Eurovent.
(2) In dB ref 20μPa, ‘A weighted. Declared dual-number noise emission values in accordance with ISO 4871 with an associated uncertainty of +/-3dB(A). For information,
calculated from the sound power Lw(A).
(3) Options : 15 = Low noise, 15LS = Very Low noise, 118a = DX freecooling option, 50= Heat recovery.
(4) Values are guidelines only. Refer to the unit name plate.
Eurovent certified
values
Eurovent certified
values
Eurovent certied
values

Table of Contents