36
4.5 - Electrical data (continued)
30XB from 1100 to 1700 with option 254 or 255 (continued)
30XB with option 254 or 255 1100 1200 1300 1400 1500 1550 1700
Maximum current (Un-10%)
(1)
Standard unit
Circuit 1
(a)
A 319 366 440 470 509 740 593
Circuit 2
(a)
A 464 509 470 505 509 370 593
Option 081 A 785 877 912 977 1020 1113
Unit + option 15LS
Circuit 1
(a)
A 309 357 424 454 491 727 574
Circuit 2
(a)
A 452 493 454 489 491 357 574
Option 081 A 762 850 880 945 985 1074
Nominal start-up current
(3)
Standard unit
Circuit 1
(a)
A 590 587 629 629 629 954 812
Circuit 2
(a)
A 635 629 629 629 629 477 812
Option 081 A 949 986 985 1015 1019 1316
Option 081 & Opt 25c A 811 820 844 862 862
Unit + option 15LS
Circuit 1
(a)
A 576 578 613 613 611 941 793
Circuit 2
(a)
A 615 613 613 613 611 464 793
Option 081 A 1020 1070 1063 1098 1099 1393
Option 081 & Opt 25c A 776 795 812 830 826
Maximum start-up current(Un)
(2)
Standard unit
Circuit 1
(a)
A 590 590 629 629 629 954 812
Circuit 2
(a)
A 635 632 629 629 629 477 812
Option 081 A 1055 1101 1095 1130 1134 1431
Option 081 & Opt 25c A 811 820 844 862 862
Unit + option 15LS
Circuit 1
(a)
A 576 578 613 613 611 941 793
Circuit 2
(a)
A 615 613 613 613 611 464 793
Option 081 A 1020 1070 1063 1098 1099 1393
Option 081 & Opt 25c A 776 795 812 830 826
(1) Values obtained at unit continuous maximum operating conditions (data given on the unit nameplate)
(2) Operating current of the smallest compressor(s) + fan current + locked rotor current or reduced start-up current of the largest compressor.
(3) Standardised EUROVENT conditions, water-cooled exchanger water inlet/outlet = 12°C/7°C, outdoor air temperature = 35°C.
(a) When the machines are equipped with two power supplies, circuit 1 supplies the refrigerant circuit A and circuit 2 supplies the refrigerant circuit B or for units 30XB1550
to 1700 units: Circuit 1 supplies circuits A and B, circuit 2 supplies circuits C and D.
4.6 - Compressor electrical data
Compressor I Nom
(1)
I Max
(Un)
(2)
I Max
(Un - 10%)
(3)
LRYA
A
(4)
LRDA
A
(5)
Cos
Phi nom.
(6)
Cos
Phi Max.
(7)
06TSA155 64 93 99 170 530 0,87 0,9
06TSA186 80 111 118 170 530 0,86 0,89
06TTA266 117 162 172 303 945 0,86 0,9
06TTA301 132 177 188 388 1210 0,87 0,9
06TTA356 153 207 220 388 1210 0,87 0,9
06TUA483 225 292 311 587 1828 0,87 0,88
06TUA554 241 338 360 587 1828 0,88 0,89
06TVA680 302 400 436 629 1919 0,87 0,89
06TVA753 315 430 468 629 1919 0,88 0,89
06TVA819 347 465 496 629 1919 0,88 0,89
Legend
(1) Nominal current draw at standard Eurovent conditions (see denition of conditions under nominal unit current draw)
(2) Maximum operating current
(3) Maximum compressor operating current, limited by the unit (current given for maximum capacity at 360 V)
(4) Locked rotor current for star connection (connection during compressor start-up)
(5) Locked rotor current for delta connection
(6) Value at standard Eurovent conditions: evaporator entering/leaving water temperature 12°C/7°C, condenser entering/leaving water temperature 30°C/35°C.
(7) Value at maximum capacity and nominal voltage
4 - PHYSICAL AND ELECTRICAL DATA FOR 30XB UNITS