EasyManua.ls Logo

Carrier AquaForce 30XB series - Electrical Data, Optional Hydraulic Module

Carrier AquaForce 30XB series
70 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
38
4.8 - Electrical data, optional hydraulic module
The pumps that are factory-installed in these units comply with the European Ecodesign directive ErP. The additional electrical
data required
(1)
is as follows:
Motors of single and dual low-pressure pumps for 30XB units (options 116F and 116G)
No.
(2)
description
(3)
250 300 350 400 450 500
1 Nominal efciency at full load and nominal voltage % 86,7 86,7 87,2 88,1 89,4 89,4
1 Nominal efciency at 75% full load and nominal voltage % 87,0 87,0 86,9 88,0 88,9 88,9
1 Nominal efciency at 50% full load and nominal voltage % 85,5 85,5 84,5 86,1 86,7 86,7
2 Efciency level - IE3
3 Year of manufacture - This information varies depending on the manufacturer and model at the time of
incorporation. Please refer to the motor nameplates.
4 Company name or trademark, commercial registration number and
head ofce of manufacturer
- Same as above
5 Product model number - Same as above
6 Number of motor poles - 2
7-1 Nominal shaft power output at full load and nominal voltage (400 V) kW 2,2 2,2 3,0 4,0 5,5 5,5
7-2 Maximum input power (400V)
(4)
kW 2,54 2,54 3,44 4,54 6,15 6,15
8 Nominal input frequency Hz 50
9-1 Nominal voltage V 3*400
9-2 Maximum current drawn (400V)
(5)
A 4,2 4,2 5,5 7,4 9,7 9,7
10 Nominal speed r/s - r/min 48 - 2900 48 - 2900 49 - 2915 49 - 2915 49 - 2930 49 - 2930
11 product disassembly, recycling or disposal at end of life - Disassembly using standard tools. Disposal and recycling using an appropriate
company.
12 Operating conditions for which the motor is specically designed
I - Altitudes above sea level m < 1000
(6)
II - Ambient air temperature °C < 40
III - Maximum operating temperature °C Please refer to the operating conditions given in this manual or in the specic
conditions given in the Carrier selection programs.
IV - Potentially explosive atmospheres - Non ATEX environment
Motors of single and dual high-pressure pumps for 30XB units (options 116B and 116C)
No.
(2)
description
(3)
250 300 350 400 450 500
1 Nominal efciency at full load and nominal voltage % 88,1 89,4 89,4 90,1 91,3 91,3
1 Nominal efciency at 75% full load and nominal voltage % 88,0 88,9 88,9 89,7 91,4 91,4
1 Nominal efciency at 50% full load and nominal voltage % 86,1 86,7 86,7 87,9 90,3 90,3
2 Efciency level - IE3
3 Year of manufacture - This information varies depending on the manufacturer and model at the time of
incorporation. Please refer to the motor nameplates.
4 Company name or trademark, commercial registration number and
head ofce of manufacturer
- Same as above
5 Product model number - Same as above
6 Number of motor poles - 2
7-1 Nominal shaft power output at full load and nominal voltage (400 V) kW 4 5,5 5,5 7,5 11 11
7-2 Maximum input power (400V)
(4)
kW 4,5 6,2 6,2 8,3 12,0 12,0
8 Nominal input frequency Hz 50
9-1 Nominal voltage V 3*400
9-2 Maximum current drawn (400V)
(5)
A 7,4 9,7 9,7 13,2 18,7 18,7
10 Nominal speed r/s - r/min 49 - 2915 49 - 2930 49 - 2930 49 - 2935 49 - 2945 49 - 2945
11 product disassembly, recycling or disposal at end of life - Disassembly using standard tools. Disposal and recycling using an appropriate
company.
12 Operating conditions for which the motor is specically designed
I - Altitudes above sea level m < 1000
(6)
II - Ambient air temperature °C < 40
III - Maximum operating temperature °C Please refer to the operating conditions given in this manual or in the specic
conditions given in the Carrier selection programs.
IV - Potentially explosive atmospheres - Non ATEX environment
(1) Required by regulation No. 640/2009 concerning the application of directive 2009/125/EC on the eco-design requirements for electric motors.
(2) Item number imposed by regulation No. 640/2009, annex I2b.
(3) Description given by regulation No. 640/2009, annex I2b.
(4) To obtain the maximum input power for a unit with hydraulic module, add the maximum unit input power from the electrical data table to the pump power input.
(5) To obtain the maximum unit operating current draw for a unit with hydraulic module, add the maximum unit current draw from the electrical data table to the pump current
draw.
(6) Above 1000 m, a degradation of 3% for each 500 m should be taken into consideration.
4 - PHYSICAL AND ELECTRICAL DATA FOR 30XB UNITS

Table of Contents