Carrier AquaForce 30XB series - Heat Reclaim Condenser Option (Option 50); Physical Data with Heat Reclaim Option

Carrier AquaForce 30XB series
70 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
50
9.1 - Physical data,30XB & XBP units with heat reclaim condenser option
30XB &XBP heat reclaim mode 250 300 350 400 450 500 600 700 750 800 850 900 1000
Operating weight* kg 3370 3404 3425 4102 4245 4601 5551 5782 6065 6382 6430 6805 7272
Condenser diameter in 10 10 10 12 14 14 12+12 12+12 14+12 14+12 14+12 14+14 14+14
Refrigerant charge
Circuit A kg 37 35 35 51 52 59 58 58 65 69 72 69 91
Circuit B kg 39 37 37 37 37 36 59 62 58 65 63 76 89
Heat reclaim condenser Flooded multi-pipe condenser
Water volume l 38 38 38 55 68 68 55+55 55+55 68 + 55 68 + 55 68 + 55 68+68 68+68
Water connections Type Victaulic
Nominal diameter in 3 3 3 4 4 4 4 4 4 4 4 4 4
Actual outside diameter mm 88,9 88,9 88,9 114,3 114,3 114,3 114,3 114,3 114,3 114,3 114,3 114,3 114,3
* Weights are for guidance only
9.2 - Dimensions, clearances
9.2.1 - 30XB-250 to 350 - heat reclaim option
ATTENTION: The condenser connection sleeves are not
installed, but supplied with the unit. The sealing joints are in
the control box. The temperature sensors and the condenser
ow switch are wired and xed in the machine. They must be
installed as described in the chapter “Condenser water
connections”.
NOTES:
- Drawings are not contractually binding.
- Before designing an installation, consult the certied
dimensional drawings, available on request.
- For the positioning of the fixing points, weight
distribution and centre of gravity coordinates please
refer to the dimensional drawings.
- If the installation includes several units or if this
(these) is (are) close to walls, please refer to chapters
3.11 - “Multiple chiller installation” and 3.12 -
“Distance to the wall” of this document to determine
the space required.
Legend
All dimensions are given in mm.
1
Required clearances for maintenance (see note)
2
Recommended space for evaporator tube removal
Water inlet for standard unit
For options 5, 6, 100A, 100C, 107 refer to the certied
drawing.
Water outlet
For options 5, 6, 100A, 100C, 107 refer to the certied
drawing.
Air outlet – do not obstruct
Power supply and control connection
A
Heat reclaim condenser
9 - HEAT RECLAIM CONDENSER OPTION (OPTION 50)