Electrical Schematics — Control and power schemat-
ics for 30XV units with Greenspeed
®
intelligence are shown in
Figs. 70-81.
Quick Test (Service Test) — Main power and control
circuit power must be on for Quick Test. The Touch Pilot™
Quick Test function is used to verify proper operation of vari-
ous devices within the chiller, such as condenser fans, automat-
ed isolation valves, EXVs, and remote alarm relays. This is
helpful during the start-up procedure to determine if devices
are installed correctly.
To use the Quick Test mode, the Enable/Off/Remote Con-
tact switch must be in the OFF position. To reach the Quick
Test menu, follow the path: Main Menu Quick Test Table.
The unit must be in Local Off mode to adjust parameters in the
table. The Quick Test function is not available remotely, and
can only be used from the Touch Pilot display. See the Start-Up
Checklist at the end of this document, page CL-6, for a list of
the parameters in the Quick Test Table.
Example: Test the function of the Ckt A condenser fans
Power must be applied to the unit. The Enable/Off/
Remote Contact switch must be in the OFF position.
Press the Start/Stop button and ensure the unit is in Local
Off.
Navigate to the Quick Test table and set line 2 Quick Test
Enable to Enable.
Set line 12, VariFan Speed A, to 100%, then select the
Force icon to accept the entry. Confirm all fans are
running.
Test component function by turning the item values from
OFF to ON or adjusting the actuated percentage. These discrete
outputs are then turned off if there is no keypad activity for 10
minutes.
NOTE: There may be up to a one-minute delay before the
selected item is energized.
LEGEND FOR FIG. 70-81
ALM Alarm GFI-CO Ground Fault Interrupter - Convenience Outlet
AUX Auxiliary GND Ground
ALT Alert HPS High-Pressure Switch
CB Circuit Breaker HTR Heater
CLR Evaporator LIQ Liquid
COMPR Compressor NEC National Electrical Code
CSR Current Sensing Relay OPT Oil Pressure Transducer
CWFS Chilled Water Flow Switch PMP Pump
DGT Discharge Gas Temperature SGT Suction Gas Temperature
DPT Discharge Pressure and Temperature SHD Loadshed
ECTA Economizer A Temp SIOB Standard Input/Output Board
ECTB Economizer B Temp SPT Space Temperature
EMM Energy Management Module TB Terminal Block
EPT Economizer Pressure Transducer TRAN Transformer
EXV Electronic Expansion Valve VFD Variable Frequency Drive
FIOP Factory-Installed Option UPC Universal Protocol Converter
FM Fan Motor XL Across the Line
FU Fuse