129
APPENDIX A — TOUCH PILOT™ DISPLAY TABLES
GENERAL PARAMETERS
GENERAL CONFIGURATION
LEGEND
CCN TABLE NAME: GENUNIT
TABLE TYPE: 11H
TOUCH PILOT PATH: Main Menu General Parameters
LINE TOUCH PILOT DESCRIPTION CCN NAME RANGE
DEFAULT
VALUE
UNIT
READ/
WRITE
1 Local = 0 Net. = 1 Remote = 2 CTRL_TYP 0 to 3 0 - RO
2 Run Status STATUS - RO
3 Net.: Cmd Start/Stop CHIL_S_S 0 to 1 0 - RW
4 Net.: Cmd Occupied CHIL_OCC 0 to 1 0 - RW
5 Minutes Left for Start min_left 0 min RO
6 Setpoint Select SP_SEL 0 to 2 0 - RW
7 0=Auto, 1=Spt1, 2=Spt2 text 8 char -
8 Setpoint Occupied? SP_OCC 0 to 1 1 - RW
9 Percent Total Capacity CAP_T 0 % RO
10 Current Setpoint SP 0 °F RO
11 Control Point CTRL_PNT -4.0 to 153.0 0 °F RW
12 Emergency Stop EMSTOP 0 to 1 0 - RW
13 Active Demand Limit Val DEM_LIM 0 to 100 0 % RW
14 Demand Limit Minimum min_lim 0 to 100 100 % RO
15 SW Version VERS_ID - RO
CCN TABLE NAME: GEN_CONF
TABLE TYPE: 12H
TOUCH PILOT PATH: Main Menu Configuration Menu General Configuration
LINE TOUCH PILOT DESCRIPTION CCN NAME RANGE
DEFAULT
VALUE
UNIT
READ/
WRITE
1 Cir Priority Sequence prio_cir 0 to 2 0 - RO
2 0 = Auto, 1 = A Prio -
3 2 = B Prio -
4 Ramp Loading Enable ramp_sel no/yes 0 (no) - RO
5 Unit Off to On Delay off_on_d 1 to 15 1 min RO
6 Demand Limit Type Select lim_sel 0 to 2 0 - RO
7 0 = None -
8 1 = Switch Control -
9 2 = 4-20mA Control -
10 Night Mode Start Hour nh_start 0 - RO
11 Night Mode End Hour nh_end 0 - RO
12 Night Capacity Limit nh_limit 0 to 100 100 % RO
13 Ice Mode Enable ice_cnfg 0 to 1 0 - RO
14 Short Cycle Management shortcyc 0 to 1 0 - RO
RO — Read Only
RW — Read/Write