130
APPENDIX A — TOUCH PILOT™ DISPLAY TABLES (cont)
PUMP CONFIGURATION
USER CONFIGURATION
RESET CONFIGURATION
LEGEND
CCN TABLE NAME: PUMPCONF
TABLE TYPE: 11H
TOUCH PILOT PATH: Main Menu Configuration Menu Pump Configuration
LINE TOUCH PILOT DESCRIPTION CCN NAME RANGE
DEFAULT
VALUE
UNIT
READ/
WRITE
1 Evap Pumps Sequence cpumpseq 0 to 4 0 - RO
2 0 = No Pump -
3 1 = One Pump Only -
4 2 = Two Pumps Auto -
5 3 = Pump#1 Manual -
6 4 = Pump#2 Manual -
7 Pump Auto Rotation Delay pump_del 24 to 3000 48 hours RO
8 Pump Sticking Protection pump_per no/yes 0 (no) - RO
9 Flow Checked If Pump Off pump_loc no/yes 1 (yes) - RO
CCN TABLE NAME: USERCONF
TABLE TYPE: 11H
TOUCH PILOT PATH: Main Menu Configuration Menu User Configuration
LINE TOUCH PILOT DESCRIPTION CCN NAME RANGE
DEFAULT
VALUE
UNIT
READ/
WRITE
1 User Password use_pass 1 to 9999 11 RO
CCN TABLE NAME: RESETCFG
TABLE TYPE: 11H
TOUCH PILOT PATH: Main Menu Configuration Menu Reset Configuration
LINE TOUCH PILOT DESCRIPTION CCN NAME RANGE
DEFAULT
VALUE
UNIT
READ/
WRITE
1 Cooling Reset Select cr_sel 0 to 4 0 - RO
2 0=None, 1=OAT -
3 2=Delta T, 4=Space Temp -
4 3=4-20mA control -
5 -
6 Cooling -
7 OAT No Reset Value oat_crno 14 to125 14 (-10) °F (°C) RO
8 OAT Full Reset Value oat_crfu 14 to125 14 (-10) °F (°C) RO
9 Delta T No Reset Value dt_cr_no 0 to 25 0 °F(°C) RO
10 Delta T Full Reset Value dt_cr_fu 0 to 25 0 °F(°C) RO
11 Current No Reset Value v_cr_no 0 to 25 0 mA RO
12 Current Full Reset Value v_cr_fu 0 to 20 0 mA RO
13 Space T No Reset Value spacr_no 14 to125 14 (-10) °F (°C) RO
14 Space T Full Reset Value spacr_fu 14 to125 14 (-10) °F (°C) RO
15 Cooling Reset Deg. Value cr_deg -30 to 30 0 °F(°C) RO
RO — Read Only