APPENDIX I — COMPRESSOR CIRCUIT BREAKER FACTORY TRIP SETTINGS
Table B — Mid/High Tier*
Table C — Standard Tier*
LEGEND
*Unit tier is designated by 10th character in the model number.
S = Standard Tier, M = Mid Tier and H = High Tier.
UNIT SIZE V-HZ (3 PH) BREAKER AMPS
STANDARD
SCCR
FACTORY TRIP
SETTING
HIGH SCCR
FACTORY TRIP
SETTING
30XV140-200 200 800 MDL3800W 4 HMDL3800W 4
30XV140-200 380 400 KD3400W 5 HKD3400W 5
30XV140-200 460, 575 300 KD3300W 5 HKD3300W 5
30XV225-325 380, 460, 575 500 LD3500W 5 HLD3500W 5
UNIT SIZE V-HZ (3 PH) BREAKER AMPS
STANDARD
SCCR
FACTORY TRIP
SETTING
HIGH SCCR
FACTORY TRIP
SETTING
30XV140-200 200 800 MDL3800W 4 HMDL3800W 4
30XV140-200 380, 460, 575 300 KD3300W 5 HKD3300W 5
30XV225-325 380, 460, 575 500 LD3500W 5 HLD3500W 5
SCCR Short Circuit Current Rating