EasyManua.ls Logo

Carrier AquaForce 30XV140 - EXTERNALLY POWERED (4 to 20 Ma) DEMAND

Carrier AquaForce 30XV140
178 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
39
Switch Controlled
— If using 2 or 3-step demand limit con-
trol, an energy management module must be installed. One-
step demand limit control does not require the energy manage-
ment module. To configure demand limit for switch control,
three parameters for 1-step switch control must be configured.
For 2 or 3-step control, additional set point parameters must be
configured. The parameters are: the type of Demand Limit Se-
lection, the setting for Switch Limit Setpoint 1, the setting for
Switch Limit Setpoint 2 (if required) and the setting for Switch
Limit Setpoint 3 (if required).
To configure this option with the Touch Pilot™ display:
In the following example, 2-step demand limit based on
capacity is desired with the first switch closure limiting the
capacity to 60%. The second switch closure is to limit the ca-
pacity to 40%. Demand Limit Switch 1 is 60% and Demand
Limit Switch 2 is 40%. Since no third-step demand limit is re-
quired, Switch Limit Setpoint 3 is set at 0%.
EXTERNALLY POWERED (4 to 20 mA) DEMAND
LIMIT — The energy management module is required for 4 to
20 mA demand limit control. An externally powered 4 to 20 mA
signal must be connected to TB6-1 and TB6-2. Typically the 4 to
20mA signal is provided by an active outdoor sensor connected
to this input. This signal is read by a transducer type (0 to 5 vdc)
on the EMM board via a field-installed 0.5 W 250-ohm resistor.
Externally Powered (4 to 20 mA) Current Based Demand
Limit — To configure demand limit for 4 to 20 mA control
based on unit capacity, one parameter must be configured.
The parameter is Demand Limit Type Select. The value of
the capacity limit will vary linearly for 0% to 100% based
on the input signal where 4 mA is 100% and 20 mA is 0%
of total unit capacity.
To configure this option with the Touch Pilot display:
In the example in Fig. 36, a 4 mA signal is Demand
Limit 100% and a 20 mA Demand Limit signal is 0%. The
4 to 20 mA signal is connected to TB6-1 and TB6-2. The
demand limit is a linear interpolation between the two val-
ues entered. If the machine receives a 12 mA signal, the
machine controls will limit the capacity to 50%.
DISPLAY NAME PATH VALUE
Demand Limit
Type Select
Main Menu
Configuration Menu
General Configuration
1 (Switch)
Low = 0
Default = 0 (None)
High = 4
Switch Limit
Setpoint 1
Main Menu
Setpoint Table
Low = 0%
Default = 100%
High = 100%
Switch Limit
Setpoint 2
Main Menu
Setpoint Table
Low = 0%
Default = 100%
High = 100%
(Not required
for 1-Step Control)
Switch Limit
Setpoint 3
Main Menu
Setpoint Table
Low = 0%
Default = 100%
High = 100%
(Not required for 1 or
2-Step Control)
DISPLAY NAME VALUE
Demand Limit Type Select 1
Switch Limit Setpoint 1 60%
Switch Limit Setpoint 2 40%
Switch Limit Setpoint 3 0%
CAUTION
Care should be taken when interfacing with other control
systems due to possible power supply differences such as a
full wave bridge versus a half wave rectification. Connec-
tion of control devices with different power supplies may
result in permanent damage. Touch Pilot controls incorpo-
rate power supplies with half wave rectification. A signal
isolation device should be utilized if the signal generator
incorporates a full wave bridge rectifier.
DISPLAY NAME PATH VALUE
Demand Limit
Type Select
Main Menu
Configuration Menu 
General Configuration
2 (4-20mA Control)
(Default = 0 [None])
0
10
20
30
40
50
60
70
80
90
100
12 14 16 18
20
mA Demand Limit Signal
% Demand Limit
0
2
4 6
8 10
mA for Demand Limit = 100%
(lim_mx)
mA for Demand Limit = 0%
(lim_ze)
a30-5883
Fig. 36 — Example: 4 to 20 mA Demand Limit

Table of Contents

Related product manuals