APPENDIX H — EVAPORATOR HEATER SENSOR SET POINT
Evaporator Heater Sensor Set Point
COOLER HEATER CSR SETTINGS
TONNAGE TIER
SETPOINT [AMPS]
MODEL 12TH DIGIT
0,1,B
NO PUMP
MODEL 12TH DIGIT
2,C
NO PUMP
MODEL 12TH DIGIT
3
NO PUMP
MODEL 12TH DIGIT
4,5,6,7,D,F,J,K,L,M
PUMP OPTION
MODEL 12TH DIGIT
8,9,G,N,P
PUMP OPTION
140-180 ALL 5.2 5.2 5.2 10.4 10.4
200 S 5.2 5.2 n/a 10.4 10.4
200 M, H 10.4 5.2 5.2 15.6 10.4
225 - 325 All 10.4 10.4 10.4 15.6 15.6
350 - 500 All 10.4 10.4 10.4 n/a n/a