Electrical Schematics
Control and power schematics for 30XV units with Green-
speed
®
Intelligence are shown in Fig. 90-102.
Quick Test (Service Test)
Main power and control circuit power must be on for Quick
Test. The Carrier Controller Quick Test function is used to ver-
ify proper operation of various devices within the chiller, such
as condenser fans, automated isolation valves, EXVs, and re-
mote alarm relays. This is helpful during the start-up procedure
to determine if devices are installed correctly.
To use the Quick Test mode, the unit must be in the local OFF
mode. To reach the Quick Test menu, follow the path: Main
Menu
Quick Test Table. The unit must be in Local Off
mode to adjust parameters in the table. The Quick Test function
is not available remotely, and can only be used from the Carrier
Controller display. See the Start-Up Checklist at the end of this
document, page CL-6, for a list of the parameters in the Quick
Test Table.
Example: Test the function of the Ckt A condenser fans
Power must be applied to the unit. The Enable-Off-Remote
Contact switch must be in the OFF position.
Touch the Start/Stop button and ensure the unit is in Local
Off.
Navigate to the Quick Test table and set line 2 Quick Test
Enable to Enable.
Set line 11, VariFan Speed A, to 100%, then select SET
from the pop-up menu to accept the entry. Confirm all fans
are running.
Test component function by turning the item values from OFF to
ON or adjusting the actuated percentage. These discrete outputs
are then turned off if there is no keypad activity for 10 minutes.
See Fig. 103 and 104 for component arrangement diagrams.
NOTE: There may be up to a one-minute delay before the se-
lected item is energized.
LEGEND FOR FIG. 90-102
ALM Alarm GFI-CO Ground Fault Interrupter - Convenience Outlet
AUX Auxiliary GND Ground
ALT Alert HPS High-Pressure Switch
CB Circuit Breaker HTR Heater
CLR Evaporator LIQ Liquid
COMPR Compressor NEC National Electrical Code
CSR Current Sensing Relay OPT Oil Pressure Transducer
CWFS Chilled Water Flow Switch PMP Pump
DGT Discharge Gas Temperature SGT Suction Gas Temperature
DPT Discharge Pressure and Temperature SIOB Standard Input/Output Board
ECTA Economizer A Temp SPT Space Temperature
ECTB Economizer B Temp TB Terminal Block
EMM Energy Management Module TRAN Transformer
EPT Economizer Pressure Transducer VFD Variable Frequency Drive
EXV Electronic Expansion Valve UPC Universal Protocol Converter
FIOP Factory-Installed Option XL Across the Line
FM Fan Motor
FU Fuse