4.2 - Electrical data
30XW-V/30XWHV 580 630 810 880 1150 1280 1470 1570 1710
Power circuit
Nominal power supply V-ph-Hz 400-3-50
Voltage range V 360-440
Control circuit 24 V via the built-in transformer
Start-up current
(1)
A Negligible (lower than maximum current drawn)
Maximum power factor
(2)
0,91-
0,93
0,91-
0,93
0,91-
0,93
0,91-
0,93
0,91-
0,93
0,91-
0,93
0,91-
0,93
0,91-
0,93
0,91-
0,93
Cosine phi > 0,98 > 0,98 > 0,98 > 0,98 > 0,98 > 0,98 > 0,98 > 0,98 > 0,98
Harmonic distortion rate
(3)
% 35-45 35-45 35-45 35-45 35-45 35-45 35-45 35-45 35-45
Maximum power input
(4)
Circuit A kW 155 193 222 246 155 193 222 222 246
Circuit B kW - - - - 155 193 193 222 246
With option 81 kW - - - - 310 386 415 444 492
Eurovent current draw
†
Circuit A A 175 200 240 265 175 200 240 240 265
Circuit B A - - - - 175 200 200 240 265
With option 81 A - - - - 350 400 440 480 530
Maximum current draw (Un)
(4)
Circuit A A 245 300 346 383 245 300 346 346 383
Circuit B A - - - - 245 300 300 346 383
With option 81 A - - - - 490 600 646 692 766
Maximum current draw (Un -10%)
(3)
Circuit A A 270 330 380 421 270 330 380 380 421
Circuit B A - - - - 270 330 330 380 421
With option 81 A - - - - 540 660 710 760 842
Maximum power input with option 150B
(4)
Circuit A kW 141 173 199 221 141 173 199 199 221
Circuit B kW - - - - 141 173 173 199 221
With option 81 kW - - - - 282 346 372 398 442
Maximum current draw (Un) with option 150B
(4)
Circuit A A 222 272 314 348 222 272 314 314 348
Circuit B A - - - - 222 272 272 314 348
With option 81 A - - - - 444 544 586 628 696
Dissipated power
(3)
W 3000 4200 4700 5300 6000 8400 8900 9400 10600
(1) Instantaneous start-up current.
(2) May vary, based on the short-circuit current/max. current draw ratio of the system transformer. Values obtained at operation with maximum unit power input.
(3) Values obtained at operation with maximum unit power input.
(4) Values obtained at operation with maximum unit power input. Values given on the unit name plate.
† Eurovent unit operating conditions: evaporator entering/leaving water temperature = 12°C/7°C, condenser entering/leaving water temperature = 30°C/35°C.
Gross performances, not in accordance with EN14511-3:2013. These performances do not take into account the correction for the proportional heating capacity and
power input generated by the water pump to overcome the internal pressure drop in the heat exchanger.
4 - PHYSICAL AND ELECTRICAL DATA