7.2 - Water connections
The water connections are Victaulic type connections. The inlet and outlet connection diameters are identical.
Inlet/outlet diameters
Evaporator 30XW-V/30XWHV 580 630 810 880 1150 1280 1470 1570 1710
Units without option 100C
Connection in 6 6 8 8 8 8 8 8 8
Outside diameter mm 168,3 168,3 219,1 219,1 219,1 219,1 219,1 219,1 219,1
Units with option 100C
Connection in 6 6 8 8 8 8 8 8 8
Outside diameter mm 168,3 168,3 219,1 219,1 219,1 219,1 219,1 219,1 219,1
Condenser 30XW-V/30XWHV 580 630 810 880 1150 1280 1470 1570 1710
Units without option 102C
Connection in 6 6 8 8 8 8 8 8 8
Outside diameter mm 168,3 168,3 219,1 219,1 219,1 219,1 219,1 219,1 219,1
Units with option 102C
Connection in 8 8 8 8 8 8 8 8 8
Outside diameter mm 219,1 219,1 219,1 219,1 219,1 219,1 219,1 219,1 219,1
7.3 - Flow control
Evaporator ow switch and chilled water pump interlock
IMPORTANT: On 30XW-V/30XWHV units, the unit water ow
switch must be energised. Failure to follow this instruction
will void the Carrier guarantee.
The water ow  switch is installed on the evaporator  water inlet 
and adjusted by the control, based on unit size and application. If 
adjustment  is  necessary,  it  must  be  carried  out  by  qualied 
personnel trained by Carrier Service.
7.4 - Evaporator and condenser water box bolt
tightening
The evaporator (and condenser) are of the shell and tube type
with removable water boxes to facilitate cleaning. Re-tightening
or tightening must be done in accordance with the illustration in
the example below.
Water box tightening sequence
Legend
1 Sequence 1: 1 2 3 4 2 Tightening torque
Sequence 2: 5 6 7 8 Bolt size M16 - 171 - 210 Nm
Sequence 3: 9 10 11 12
Sequence 4: 13 14 15 16
NOTE: Before this operation we recommend draining the
circuit and disconnecting the pipes to be sure that the bolts
are correctly and uniformly tightened.