205
Table 165 — VFD Parameters, High Tier, for 440 V/50 Hz Units, 30XV350-450
NOTE: Compressor motor voltage is 380V.
PARAMETER
SETTING
DESCRIPTION
30XV350 30XV400 30XV450
COMP FAN COMP FAN COMP FAN
NUMBERDESCRIPTION A B A1A2B1B2 A B A1A2B1B2 A B A1A2B1B2
0-40
hand on
button
disabled 0 0 N/A N/A N/A N/A 0 0 N/A N/A N/A N/A 0 0 N/A N/A N/A N/A
1-03 torque profile
Compressor
Torque
0 0 N/A N/A N/A N/A 0 0 N/A N/A N/A N/A 0 0 N/A N/A N/A N/A
1-20 motor kW
size
dependent
242 160 13.8 11.5 11.5 9.2 242 242 13.8 11.5 13.8 11.5 242 242 13.8 13.8 13.8 13.8
1-22 motor volts
motor
dependent
380 380 380 380 380 380 380 380 380 380 380 380 380 380 380 380 380 380
1-23
motor
frequency
motor
dependent
95 98 60 60 60 60 95 95 60 60 60 60 95 95 60 60 60 60
1-24
motor
amperage
size
dependent
469 340 42.6 35.5 35.5 28.4 492 492 42.6 35.5 42.6 35.5 533 533 42.6 42.6 42.6 42.6
1-25 motor rpm
size
dependent
5650 5830 1130 1130 1130 1130 5650 5650 1130 1130 1130 1130 5650 5650 1130 1130 1130 1130
1-71
compressor
start delay
0s 0 0 N/A N/A N/A N/A 0 0 N/A N/A N/A N/A 0 0 N/A N/A N/A N/A
1-73 Flying Restart NO N/AN/A0000N/AN/A0000N/AN/A0000
1-78
starting
frequency
26hz 26 26 N/A N/A N/A N/A 26 26 N/A N/A N/A N/A 26 26 N/A N/A N/A N/A
1-79
Comp start
maxtime to
trip
5s 5 5 N/A N/A N/A N/A 5 5 N/A N/A N/A N/A 5 5 N/A N/A N/A N/A
1-80
function at
stop
coast 000000000000000000
1-90
motor ther-
mal protection
0 000000000000000000
3-02 min ref 0 0 0 N/A N/A N/A N/A 0 0 N/A N/A N/A N/A 0 0 N/A N/A N/A N/A
3-03 max reference
size
dependent
75 90 60 60 60 60 75 75 60 60 60 60 84 84 60 60 60 60
3-13 type reference remote 110000110000110000
3-15 src ref#1 no function 000000000000000000
3-16 src ref#2 no function 000000000000000000
3-41 ramp up 100s 100 100 20 20 20 20 100 100 20 20 20 20 100 100 20 20 20 20
3-42 ramp down 100s 100 100 20 20 20 20 100 100 20 20 20 20 100 100 20 20 20 20
3-82
starting ramp
time
3s 3 3 N/A N/A N/A N/A 3 3 N/A N/A N/A N/A 3 3 N/A N/A N/A N/A
4-10
motor speed
direct
clockwise 000000000000000000
4-12
motor speed
low limit
26Hz 262655552626555526265555
4-14
motor speed
high limit
95Hz 75 90 60 60 60 60 75 75 60 60 60 60 84 84 60 60 60 60
4-16 torque limit
size
dependent
150 150 150 150 150 150 150 150 150 150 150 150 150 150 150 150 150 150
4-18 current limit
size
dependent
110 110 110 110 110 110 110 110 110 110 110 110 110 110 110 110 110 110
4-19
max output
frequency
size
dependent
76 91 N/A N/A N/A N/A 76 76 N/A N/A N/A N/A 85 85 N/A N/A N/A N/A
5-12 DI #27 Coast Inverse 220000220000220000
5-19
DI#37 safe
stop
safe stop
alarm
1 1 N/A N/A N/A N/A 1 1 N/A N/A N/A N/A 1 1 N/A N/A N/A N/A
5-40[36] relay 1
control word
bit 11
36 36 N/A N/A N/A N/A 36 36 N/A N/A N/A N/A 36 36 N/A N/A N/A N/A
5-40[5] relay 2 running 5 5 N/A N/A N/A N/A 5 5 N/A N/A N/A N/A 5 5 N/A N/A N/A N/A
8-01 control site
digital & con-
trol word
000000000000000000
8-02
control
source
FC
port=RS485
111111111111111111
8-03 time out time 10s 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10
8-04
time out func-
tion
stop and trip 552222552222552222
14-00 Pattern [AVM] 60AVM N/AN/A0000N/AN/A0000N/AN/A0000
14-01
switching
frequency
3kHz 446666446666446666
14-03
over-
modulation
yes 1 1 N/A N/A N/A N/A 1 1 N/A N/A N/A N/A 1 1 N/A N/A N/A N/A
14-10 main failure alarm 6 6 N/A N/A N/A N/A 6 6 N/A N/A N/A N/A 6 6 N/A N/A N/A N/A
14-11
Mains voltage
at Mains fault
345V 352 352 N/A N/A N/A N/A 352 352 N/A N/A N/A N/A 352 352 N/A N/A N/A N/A
14-50 RFI Filter on 1 1 N/A N/A N/A N/A 1 1 N/A N/A N/A N/A 1 1 N/A N/A N/A N/A
14-60
function at
overtemp
derate 1 1 N/A N/A N/A N/A 1 1 N/A N/A N/A N/A 1 1 N/A N/A N/A N/A
14-61
inverter
overload
derate 1 1 N/A N/A N/A N/A 1 1 N/A N/A N/A N/A 1 1 N/A N/A N/A N/A