number must be changed to configure the unit to broadcast a
Global Time Schedule. The Schedule Number can be set from
65 to 99 (OCCPC65S to OCCPC99S). When OCC1PxxS is set
to a value of 65 or greater and all attached schedules are 00:00
(that is, no occupied time periods), an occupancy flag is broad-
cast over the CCN every time it transitions from occupied to
unoccupied or vice-versa. The ComfortVIEW™ Network
Manager’s Configure and Modify commands or the Service
Tool’s Modify/Names function must be used to change the
number of the Occupancy Equipment Part Table Name (OC-
CPC01E) to the Global Schedule Number. The Schedule Num-
ber can be set from 65 to 99 (OCCPC65E to OCCPC99E).
Table 23 — Active Cooling Set Point Parameters
* Ice Storage Configuration and Ice Done Contact apply only to units
with EMM.
OPERATING
TYPE
PARAMETER STATUS
ACTIVE SETPOINT
Setpoint
Selection
Ice Storage
Configuration*
Ice Done
Contact*
Setpoint
Switch
Schedule 2 Status
Local
sp-1 Default Any Any Default Cooling Setpoint 1
sp-2 No Any Any Default Cooling Setpoint 2
sp-2 Yes Closed Any N/A Cooling Setpoint 2
sp-2 Yes Open Any N/A Cooling Ice Setpoint
automatic Default Any Any Occupied Cooling Setpoint 1
automatic No Any Any Unoccupied Cooling Setpoint 2
automatic Yes Closed Any Unoccupied Cooling Setpoint 2
automatic Yes Open Any Unoccupied Cooling Ice Setpoint
Remote
Default Default Any Open Default Cooling Setpoint 1
Default No Any Closed Default Cooling Setpoint 2
N/A Yes Closed Closed N/A Cooling Setpoint 2
Default Yes Open Closed Default Cooling Ice Setpoint
Network
Default Default Any Any Occupied Cooling Setpoint 1
Default Default Any Any Unoccupied Cooling Setpoint 2