APPENDIX B — CCN POINT TABLE (cont)
See Legend on page 307.
Maintenance\M_MSTSLV - Master Slave Control
DESCRIPTION VALUE UNITS POINT NAME
TRANSLATOR
ACCESSIBLE
NETWORK
ACCESS
Max Available Capacity No/Yes cap_max N N/A
Slave lagstat lagstat N N/A
Slave Operating Hours hours slav_hr N N/A
Slave Evap Ent. Fluid °F (°C) slav_ewt N N/A
Slave Evap Leav. Fluid °F (°C) slav_lwt N N/A
Maintenance\QCK_TEST - Quick Test
DESCRIPTION VALUE UNITS POINT NAME
TRANSLATOR
ACCESSIBLE
NETWORK
ACCESS
Unit must be in L-off YRW
Quick Test Enable Disable/Enable QCK_TEST Y RW
Circuit A EXV Position 0 to 100 % Q_EXVA Y RW
Circuit A Oil Solenoid Off/On Q_OILS_A Y RW
EXV Eco Position Cir A 0-100 % Q_ECO_A Y RW
Oil Heater Circuit A Off/On Q_OILHTA Y RW
Capacity Cir A Output 0 to 100 % Q_010_A Y RW
Comp A Running Output Off/On Q_COMPA Y RW
Isolation Valve State A Close/Open Q_ISOP_A Y RW
Circuit A VI Off/On Q_VI_A Y RW
VariFan Speed A 0 to 100 % Q_VFAN_A Y RW
Circuit B EXV Position 0 to 100 % Q_EXVB Y RW
Circuit B Oil Solenoid Off/On Q_OILS_B Y RW
EXV Eco Position Cir B 0 to 100 % Q_ECO_B Y RW
Oil Heater Circuit B Off/On Q_OILHTB Y RW
Capacity Cir B Output 0 to 100 % Q_010_B Y RW
Comp B Running Output Off/On Q_COMPB Y RW
Isolation Valve State B Close/Open Q_ISOP_B Y RW
Circuit B VI Off/On Q_VI_B Y RW
VariFan Speed B 0 to 100 % Q_VFAN_B Y RW
Evaporator Heater Off/On Q_CL_HTR Y RW
Evaporator Pump 1 Q_CPMP1 Y RW
Evaporator Pump 2 Q_CPMP2 Y RW
Alarm Relay Status Off/On Q_ALARM Y RW
Shutdown Relay Status Off/On Q_SHUTD Y RW
Running Relay Status Off/On Q_RUN Y RW
Alert Relay Switch Off/On Q_ALERT Y RW