APPENDIX E — BACNET IP POINTS (cont)
LEGEND
OBJECT NAME OBJECT TYPE INSTANCE OPTION PV ACCESS DESCRIPTION
M_MSTSLV_slv_capt AV 181 RO Slave Chiller Total Cap
M_MSTSLV_slv_stat AV 180 RO Slave Chiller State
MODES_m_2stpt BV 64 IR RO Second Setpoint In Use
MODES_m_delay BV 63 IR RO Start Up Delay In Effect
MODES_m_demlim BV 66 IR RO Demand Limit Active
MODES_m_ice BV 71 IR RO Ice Mode In Effect, Active Alarms:
MODES_m_night BV 69 IR RO Night Low Noise Active
MODES_m_pmpper BV 68 IR RO Pump Periodic Start
MODES_m_pmprot BV 67 IR RO Evaporator Pump Rotation
MODES_m_reset BV 65 IR RO Reset In Effect
MODES_m_slave BV 70 IR RO Master Slave Active
MST_SLV_lag_mini AV 402 RO Lag Minimum Running Time
MST_SLV_lag_pump AV 403 RO
Lag Unit Pump Control, 0=Stop if Unit Stops, 1=Run if
Unit Stops
MST_SLV_lead_pul AV 400 RO Lead Pulldown Time
MST_SLV_lead_sel AV 397 RO
Lead Lag Select, 0=Always Lead, 1=Lag Once Failed
Only, 2=Lead/Lag Runtime Sel
MST_SLV_ll_bal_d AV 398 RO Lead/Lag Balance Delta
MST_SLV_ll_serie BV 116 RO Chiller In Series
MST_SLV_lstr_tim AV 399 RO Lead/Lag Start Timer
MST_SLV_ms_ctrl AV 395 RO
Master Control Type, 1=Local Control, 2=Remote Con-
trol, 3=CCN Control
MST_SLV_ms_sel AV 394 RO Master/Slave Select, 0=Disable, 1=Master, 2=Slave
MST_SLV_slv_addr AV 396 RO Slave Address
MST_SLV_start_dt AV 401 RO Start If Error Higher
OUTPUTS_ALARM BV 34 IR RO Alarm Relay Status
OUTPUTS_ALERT BV 36 IR RO Alert Relay State
OUTPUTS_BOX_HTR BV 57 IR RO Control Box Heater
OUTPUTS_C_HEATER BV 38 IR RO Evap Heater Output
OUTPUTS_CAPT_010 AV 70 IR RO Chiller Capacity Signal
OUTPUTS_CAPT010A AV 66 IR RO Capacity Signal Cir A
OUTPUTS_CAPT010B AV 68 IR RO Capacity Signal Cir B
OUTPUTS_CP_A BV 21 IR RO Compressor A
OUTPUTS_CP_B BV 28 IR RO Compressor B
OUTPUTS_FCA1 BV 39 IR RO Fan Contactor 1A
OUTPUTS_FCA2 BV 40 IR RO Fan Contactor 2A
OUTPUTS_FCA3 BV 41 IR RO Fan Contactor 3A
OUTPUTS_FCA4 BV 42 IR RO Fan Contactor 4A
OUTPUTS_FCA5 BV 43 IR RO Fan Contactor 5A
OUTPUTS_FCA6 BV 44 IR RO Fan Contactor 6A
OUTPUTS_FCA7 BV 45 IR RO Fan Contactor 7A
OUTPUTS_FCA8 BV 46 IR RO Fan Contactor 8A
OUTPUTS_FCB1 BV 47 IR RO Fan Contactor 1B
OUTPUTS_FCB2 BV 48 IR RO Fan Contactor 2B
OUTPUTS_FCB3 BV 49 IR RO Fan Contactor 3B
OUTPUTS_FCB4 BV 50 IR RO Fan Contactor 4B
OUTPUTS_FCB5 BV 51 IR RO Fan Contactor 5B
OUTPUTS_FCB6 BV 52 IR RO Fan Contactor 6B
AV — Analog Value IR — Intrinsic Reporting
BV — Binary Value RO — Read Only
CMD — Command RW — Read Write
COV — Change of Value TL — Trend Log