APPENDIX E — BACNET IP POINTS (cont)
LEGEND
OBJECT NAME OBJECT TYPE INSTANCE OPTION PV ACCESS DESCRIPTION
OUTPUTS_FCB7 BV 53 IR RO Fan Contactor 7B
OUTPUTS_FCB8 BV 54 IR RO Fan Contactor 8B
OUTPUTS_ISO_OP_A BV 24 IR RO Ref Iso Relay Energize A
OUTPUTS_ISO_OP_B BV 31 IR RO Ref Iso Relay Energize B
OUTPUTS_ISO_POSA BV 25 IR RO Ref Iso Valve State A
OUTPUTS_ISO_POSB BV 32 IR RO Ref Iso Valve State B
OUTPUTS_LABEL_A BV 20 IR RO CIRCUIT A
OUTPUTS_LABEL_B BV 27 IR RO CIRCUIT B
OUTPUTS_OIL_HT_A BV 26 IR RO Oil Heater Output A
OUTPUTS_OIL_HT_B BV 33 IR RO Oil Heater Output B
OUTPUTS_OIL_SL_A BV 22 IR RO Oil Solenoid Output A
OUTPUTS_OIL_SL_B BV 29 IR RO Oil Solenoid Output B
OUTPUTS_RUNNING BV 35 IR RO Running Relay Status
OUTPUTS_SHUTDOWN BV 37 IR RO Shutdown Indicator State
OUTPUTS_VFAN_A AV 67 IR RO VariFan Speed A
OUTPUTS_VFAN_B AV 69 IR RO VariFan Speed B
OUTPUTS_VFD_EN_A BV 55 IR RO Comp. HW Enable A
OUTPUTS_VFD_EN_B BV 56 IR RO Comp. HW Enable B
OUTPUTS_VI_A BV 23 IR RO VI Solenoid Output A
OUTPUTS_VI_B BV 30 IR RO VI Solenoid Output B
PRESSURE_DOP_A AV 53 COV IR RO Delta Oil Pressure A
PRESSURE_DOP_B AV 59 COV IR RO Delta Oil Pressure B
PRESSURE_DP_A AV 50 COV IR RO Discharge Pressure A
PRESSURE_DP_B AV 56 COV IR RO Discharge Pressure B
PRESSURE_ECO_P_A AV 54 COV IR RO Economizer Pressure A
PRESSURE_ECO_P_B AV 60 COV IR RO Economizer Pressure B
PRESSURE_LIQ_P_A AV 55 COV IR RO Liquid Pressure A
PRESSURE_LIQ_P_B AV 61 COV IR RO Liquid Pressure B
PRESSURE_OP_A AV 52 COV IR RO Oil Pressure A
PRESSURE_OP_B AV 58 COV IR RO Oil Pressure B
PRESSURE_SP_A AV 51 COV IR RO Main Suction Pressure A
PRESSURE_SP_B AV 57 COV IR RO Main Suction Pressure B
PUMPCONF_cpumpseq AV 7 RO
Evap Pumps Sequence, 0 = No Pump, 1 = One Pump
Only, 2 = Two Pumps Auto, 3 = Pump#1 Manual, 4 =
Pump#2 Manual
PUMPCONF_pump_del AV 8 RO Pump Auto Rotation Delay
PUMPCONF_pump_loc BV 5 RO Flow Checked If Pump Off
PUMPCONF_pump_per BV 4 RO Pump Sticking Protection
PUMPSTAT_CPUMP_1_rd BV 58 IR RO Evap Pump #1 Command
PUMPSTAT_CPUMP_1_wr BV 124 IR CMD RW Evap Pump #1 Command
PUMPSTAT_CPUMP_2_rd BV 59 IR RO Evap Pump #2 Command
PUMPSTAT_CPUMP_2_wr BV 125 IR CMD RW Evap Pump #2 Command
PUMPSTAT_FLOW_SW BV 61 IR RO Evap Flow Switch #1
PUMPSTAT_FLOW_SWB BV 62 IR RO Evap Flow Switch #2
PUMPSTAT_ROTCPUMP_rd BV 60 IR RO Rotate Evap Pumps ?
PUMPSTAT_ROTCPUMP_wr BV 127 IR CMD RW Rotate Evap Pumps ?
RESETCFG_cr_deg AV 19 RO Cooling Reset Deg. Value
RESETCFG_cr_sel AV 10 RO
Cooling Reset Select, 0=None, 1=OAT, 2=Delta T,
4=Space Temp, 3=4-20mA control, Cooling Reset
Select
AV — Analog Value IR — Intrinsic Reporting
BV — Binary Value RO — Read Only
CMD — Command RW — Read Write
COV — Change of Value TL — Trend Log