APPENDIX E — BACNET IP POINTS (cont)
LEGEND
OBJECT NAME OBJECT TYPE INSTANCE OPTION PV ACCESS DESCRIPTION
SERVICE1_auto_sm BV 111 RO Auto Start When SM Lost
SERVICE1_cdrv_cfg BV 110 RO Send comp. drive config?
SERVICE1_ewt_cirA AV 342 RO EWT Probe on Cir A Side
SERVICE1_ewt_opt BV 105 RO Entering Fluid Control
SERVICE1_fastcapr AV 341 RO Fast Capacity Recovery
SERVICE1_fdrv_cfg BV 109 RO Send fan drive config?
SERVICE1_flui_typ AV 338 RO
Evaporator Fluid Type, 1 = Water, 2 = Med Brine, 3 =
Low Brine
SERVICE1_freez_ov AV 346 RO Freeze Override Offset
SERVICE1_freezesp AV 339 RO Brine Freeze Setpoint
SERVICE1_ftp_en BV 115 RO FTP Server
SERVICE1_heatersp AV 345 RO Evap Heater Delta Spt
SERVICE1_http_en BV 114 RO HTTP Server
SERVICE1_leak_thr AV 343 Leakage Charge Threshold
SERVICE1_leak_tmr AV 344 RO Leakage Charge Timer
SERVICE1_metric BV 108 RO Metric Units? (Blackbox)
SERVICE1_mini_lwt AV 340 RO Brine Minimum Fluid Temp
SERVICE1_odrecspd AV 350 RO Oil Delta Recover Speed
SERVICE1_odtrspd AV 348 RO Oil Delta Trigger Speed
SERVICE1_orectim AV 351 RO Oil Recover Time
SERVICE1_otrigtim AV 349 RO Oil Trigger Time
SERVICE1_RFI_conf BV 107 RO Compressor RFI Filter En
SERVICE1_ser_pass BV 106 RO Service Password
SERVICE1_ViChkEn BV 112 RW VI Self-Test Enable
SERVICE1_ViPwrChk AV 347 RW VI Self-Test Threshold
SERVICE1_vistrtdt AV 353 RO High VI Time at Start
SERVICE1_vistrten AV 354 RO Enable High VI at Start
SERVICE1_wateesys AV 352 RO Water Temp Hysteresis
SETPOINT_cramp_sp AV 553 RW Cooling Ramp Loading
SETPOINT_csp1 AV 550 RW Cooling Setpoint 1
SETPOINT_csp2 AV 551 RW Cooling Setpoint 2
SETPOINT_ice_sp AV 552 RW Cooling Ice Setpoint
SETPOINT_lim_sp1 AV 554 RW Switch Limit Setpoint 1
SETPOINT_lim_sp2 AV 555 RW Switch Limit Setpoint 2
SETPOINT_lim_sp3 AV 556 RW Switch Limit Setpoint 3
TEMP_CHWSTEMP AV 49 COV IR RO Chill Water Temp (Opt.)
TEMP_COOL_EWT AV 29 COV IR RO Evap Entering Fluid
TEMP_COOL_LWT AV 30 COV IR RO Evap Leaving Fluid
TEMP_CP_TMP_A AV 37 COV IR RO Motor Temperature Cir A
TEMP_CP_TMP_B AV 45 COV IR RO Motor Temperature Cir B
TEMP_DGT_A AV 36 COV IR RO Discharge Gas Temp Cir A
TEMP_DGT_B AV 44 COV IR RO Discharge Gas Temp Cir B
TEMP_ECO_T_A AV 38 COV IR RO EXV Eco. Tmp Cir A
TEMP_ECO_T_B AV 46 COV IR RO EXV Eco. Tmp Cir B
TEMP_LIQ_T_A AV 39 COV IR RO Liquid Temperature A
TEMP_LIQ_T_B AV 47 COV IR RO Liquid Temperature B
TEMP_OAT AV 31 COV IR RO Outdoor Air Temperature
TEMP_SCT_A AV 32 COV IR RO Saturated Cond Tmp Cir A
AV — Analog Value IR — Intrinsic Reporting
BV — Binary Value RO — Read Only
CMD — Command RW — Read Write
COV — Change of Value TL — Trend Log