97
Table 57 — VFD Parameters, Standard Tier, for 380 V/60 Hz Units, 30XV350-500
PARAMETER
NUMBER
PARAMETER
DESCRIPTION
SETTING
DESCRIPTION
30XV350 30XV400 30XV450 30XV500
COMPRESSOR COMPRESSOR COMPRESSOR COMPRESSOR
ABABABAB
0-40 hand on button
disabled 00000000
1-03 torque profile
Compressor Torque 00000000
1-20 motor kW
size dependent 242 160 242 242 242 242 242 242
1-22 motor volts
motor dependent 380 380 380 380 380 380 380 380
1-23 motor frequency
motor dependent 95 98 95 95 95 95 95 95
1-24 motor amperage
size dependent 548 397 516 516 599 599 629 629
1-25 motor rpm
size dependent 5650 5830 5650 5650 5650 5650 5650 5650
1-71 compressor start delay
0s 00000000
1-78 starting frequency
26hz 26 26 26 26 26 26 26 26
1-79 Comp start max time to trip
5s 55555555
1-80 function at stop
coast 00000000
1-90 motor thermal protection
0 00000000
3-02 min ref
0 00000000
3-03 max reference
size dependent 75 90 75 75 84 84 94 94
3-13 type reference
remote 11111111
3-15 src ref#1
no function 00000000
3-16 src ref#2
no function 00000000
3-41 ramp up
100s 100 100 100 100 100 100 100 100
3-42 ramp down
100s 100 100 100 100 100 100 100 100
3-82 starting ramp time
3s 33333333
4-10 motor speed direct
clockwise 00000000
4-12 motor speed low limit
26Hz 26 26 26 26 26 26 26 26
4-14 motor speed high limit
95Hz 75 90 75 75 84 84 94 94
4-16 torque limit
size dependent 150 150 150 150 150 150 150 150
4-18 current limit
size dependent 110 110 110 110 110 110 110 110
4-19 max output frequency
size dependent 76 91 76 76 85 85 95 95
5-12 DI #27
Coast Inverse 22222222
5-19 DI#37 safe stop
safe stop alarm 11111111
5-40[36] relay 1
control word bit 11 36 36 36 36 36 36 36 36
5-40[5] relay 2
running 55555555
8-01 control site
digital & control word
00000000
8-02 control source
FC port=RS485 11111111
8-03 time out time
10s 10 10 10 10 10 10 10 10
8-04 time out function
stop and trip 55555555
14-01 switching frequency
3kHz 44444444
14-03 overmodulation
yes 11111111
14-10 main failure
alarm 66666666
14-11 Mains voltage at Mains fault
345V 300 300 300 300 300 300 300 300
14-50 RFI Filter
on 11111111
14-60 function at overtemp
derate 11111111
14-61 inverter overload
derate 11111111