Table 58 — VFD Parameters, Standard Tier, for 400 V/60 Hz Units, 30XV140-225
NOTE: Compressor motor voltage is 380V.
PARAMETER
NUMBER
PARAMETER
DESCRIPTION
SETTING
DESCRIPTION
30XV140 30XV160 30XV180 30XV200 30XV225
COMPRESSOR COMPRESSOR COMPRESSOR COMPRESSOR COMPRESSOR
ABABABABAB
0-40 hand on button
disabled 0000000000
1-03 torque profile
Compressor Torque 0000000000
1-20 motor kW
size dependent 97 97 97 97 97 97 97 97 160 97
1-22 motor volts
motor dependent 380 380 380 380 380 380 380 380 380 380
1-23 motor frequency
motor dependent 105 105 105 105 105 105 105 105 98 105
1-24 motor amperage
size dependent 177 177 211 211 246 246 252 252 354 226
1-25 motor rpm
size dependent 6240 6240 6240 6240 6240 6240 6240 6240 5830 6240
1-71 compressor start delay
0s 0000000000
1-78 starting frequency
26hz 26 26 26 26 26 26 26 26 26 26
1-79 Comp start max time to trip
5s 5555555555
1-80 function at stop
coast 0000000000
1-90 motor thermal protection
0 0000000000
3-02 min ref
0 0000000000
3-03 max reference
size dependent 75 75 85 85 95 95 105 105 83 93
3-13 type reference
remote 1111111111
3-15 src ref#1
no function 0000000000
3-16 src ref#2
no function 0000000000
3-41 ramp up
100s 100 100 100 100 100 100 100 100 100 100
3-42 ramp down
100s 100 100 100 100 100 100 100 100 100 100
3-82 starting ramp time
3s 3333333333
4-10 motor speed direct
clockwise 0000000000
4-12 motor speed low limit
26Hz 26 26 26 26 26 26 26 26 26 26
4-14 motor speed high limit
95Hz 75 75 85 85 95 95 105 105 83 93
4-16 torque limit
size dependent 150 150 150 150 150 150 150 150 150 150
4-18 current limit
size dependent 110 110 110 110 110 110 110 110 110 110
4-19 max output frequency
size dependent 76 76 86 86 96 96 106 106 84 94
5-12 DI #27
Coast Inverse 2222222222
5-19 DI#37 safe stop
safe stop alarm 1111111111
5-40[36] relay 1
control word bit 11 36 36 36 36 36 36 36 36 36 36
5-40[5] relay 2
running 5555555555
8-01 control site
digital & control word
0000000000
8-02 control source
FC port=RS485 1111111111
8-03 time out time
10s 10 10 10 10 10 10 10 10 10 10
8-04 time out function
stop and trip 5555555555
14-01 switching frequency
3kHz 4444444444
14-03 overmodulation
yes 1111111111
14-10 main failure
alarm 6666666666
14-11 Mains voltage at Mains fault
345V 320 320 320 320 320 320 320 320 320 320
14-50 RFI Filter
on 1111111111
14-60 function at overtemp
derate 1111111111
14-61 inverter overload
derate 1111111111